【文章內(nèi)容簡介】
n operation, the flow control valve is placed between the pump and actuator. In this way, it controls the amount of fluid going into the actuator. Pump delivery in excess of the Metered amount I diverted to tank over the relief valve. With the flow control valve installed in the cylinder line as shown, flow is controlled in one direction. A check valve must be included in the flow control or placed in parallel with it for return flow. If it is desired to control directional valve. The method is highly accurate. It is used in applications where the load continually resists movement of the actuator, such as raising a vertical cylinder under load or pushing a load at a controlled speed. MeterOut Circuit Meterout control is used where the load might tend to run away. The flow control is located where it will restrict exhaust flow from the actuator. To regulate speed in both directions, the valve is installed in the tank line from the directional valve. More often control is needed in only one direction and it is placed in the line between the actuator and direction valve. Here too a bypass check valve would be required for a rapid return stroke. BleedOff Circuit In a bleedoff arrangement, the flow control is bleed off the supply line from the pump and determines the actuator speed by metering a portion of the pump delivery to tank. The advantage is that the pump operates at the pressure required by the work, since excess fluid returns to tank through the flow control instead of through the relief valve. Its disadvantage is some less of accuracy because the measured flow is to tank39。 rather into the cylinder, making the latter subject to variations in the pump delivery due to changing workloads. Bleedoff circuits should not be used in applications where there is a possibility of the load running away. Types of Flow Controls Flow control valves fall into two basic categories: pressure pensated and nonpressure pensated. The latter being used where load pressures remain relatively constant and feed rates are not too critical. They may be as simple as a fixed orifice or an adjustable needle for free valve, although more sophisticated units may even include a check valve for free flow in the reverse direction. Use of nonpressure pensated valves is somewhat limited, since flow through an orifice is essentially proportional to the square root of the pressure drop across it. This means that any appreciable change in the work load would affect the feed rate. Pressure pensated flow controls are further classified as restrictor and bypass types. Both utilize a pensator or hydrostat to maintain a constant pressure drop across an adjustable throttle. The ByPass Typebines overload protection with pressure pensated control of flow. It has a normally closed hydrostat which opens to divert fluid, in excess of the throttle setting, to the tank. Pressure required by the work load is sensed in the chamber above the hydrostat and together with a light spring tends to hole it closed. Pressure in the chamber below the hydrostat increase duo to restriction of the throttle and cause is to rise diverting any excess flow to tank when the difference in pressure is sufficient to overe the spring. This difference, usually 20 psi, is maintained across the throttle providing a constant flow regardless of the work load. Some horsepower saving is acplished in that the pump need operate at only 20 psi above work load pressure. Overload protection is provided by an adjustable spring loaded poppet which limits the maximum pressure above the hydrostat, causing it to function as a pound relief valve whenever work load requirement exceed its setting. The bypass flow control can only be used in a meterin circuit. If used for metering out, exhaust oil which could not get through the throttle would be diverted to tank permitting the load to run away. The Restrictor Type Flow Controlalso maintains a constant 20 psi differential across its throttle by means of a hydrostat. In this valve, the hydrostat is normally epen and tends to close off blocking all flow in excess of the throttle setting. In these units the work load pressure acts with a light spring above the hydrostat to hold it open. Pressure at the throttle inlet and under the hydrostat tend to close it, permitting only that oil to enter the valve that 20 psi can force through the throttle. Because of their tendency close off when flow tales to exceed the throttle setting, restrictor type valves may be used in meterin, meterout and bleedoff circuits. Unlike the bypass type , two or more restrictor valves may be used with the same pump since the excess pump delivery returns to tank through the relief valves. When placed in cylinder lines an integral check valve is optional to provide free flow for a rapid return stroke. One would not be required for valves placed in the main supply line, the tank line of a directional valve or when they are used in bleedoff circuits. Temperature Compensated Flow Control Valve Flow through a pressure pensated flow control valve is subject to change with variations in oil temperature. Later design Vickers valves incorporate a temperature. Although oil flows more freely when it is hot, constant flow can be maintained by decreasing the size of the throttle opening as the temperature rises. This is acplished through a pensating rod which lengthens with heat and contracts when cold. The throttle is a simple plunger that is moved in and out of the control port. The pensating is installed between the throttle and its adjuster. This design also is available with a reverse freeflow check valve. Remote Flow Control Valves Remote flow control valves permit adjustment of the throttle size by an electrical signal. The throttle spool is linked to armature of a torque motor and moves in response to signal to the torque motor. Operation is otherwise the s