工廠設(shè)計噪音安全慣例(1)(編輯修改稿)

2025-06-12 18:57 本頁面
 

【文章內(nèi)容簡介】 stores 65 Toilets, locker rooms 60 Kitchens 60 Central Control Room 55 Laboratories 55 ADMINISTRATIVE AND OFFICE AREAS Area dBA Dining Rooms 55 Rest Rooms 50 General office areas 50 Individual office 45 Conference Room 40 Medical facilities 40 In these areas where the ventilation equipment is expected to be the principal noise source, it shall be designed to avoid excessive hiss and rumble. COMMUNITY NOISE REQUIREMENTS At the nearest Community boundary to the SECCO Plant the noise level due to the plant shall not exceed the following: Time Level (dBA) at Community boundary due to SECCO plant Day 60 Night 50 SECCO Plant Design Noise Philosophy PH00TSCSE0004A00 Plant Design Noise Philosophy Page 8 of 19 26/06/02 This plant noise requirement includes a small margin for background noise including other plant adjacent to the SECCO plant. It is based on the requirement for total noise at the Community boundary to be less than the following when all plants in the plex are operating: Time Total level (dBA) at Community boundary Day 65 Night 55 This shall be based on a measurement (sampling) time of not more than 15 minutes daytime and not more than 10 minutes at night. If any equipment to be used on the plant has an annoying tonal / narrowband noise characteristic then for the plant as a whole narrowband noise from equipment should be reduced in the relevant octave bands so it is below the broadband noise by the following amounts: Reduction of Sound Pressure Level (dB) 63 125 250 500 1k 2k 4k 8k Narrow Band Weighting Community noise 1 5 9 11 12 12 8 REPORT REQUIREMENTS The Contractor shall produce noise reports, equipment and acoustic treatment schedules, and noise level plans to show the following information. Noise reports, to give noise design requirements, summary of significant noiseemitting equipment in each area, giving noise levels expected, acoustic treatment included in the design, and any particular features or considerations incorporated. Equipment noise schedules, to give list of equipment noise levels specified / ordered / Supplier data. Acoustic treatment schedules, to give lists of pipe lines requiring acoustic insulation, including insulation type, thickness and extent. Noise plans, to show expected noise levels in each area. In addition Process Pamp。ID39。s shall include extents of pipework acoustic insulation. SECCO Plant Design Noise Philosophy PH00TSCSE0004A00 Plant Design Noise Philosophy Page 9 of 19 26/06/02 These reports, schedules and plans shall be issued to Owner and approved by him, at two stages in the project. The first report stage shall be near the end of initial design, and early enough to allow time for review by Owner before end of initial design. For this reporting stage, the initial noise design shall have been pleted. The reports and schedules shall include planned individual noise level requirements for all significant equipment and any anticipated acoustic treatment, whether or not included in equipment requisitions at that stage. The noise plans shall show anticipated noise levels in each area. Anticipated pipework acoustic insulation requirements shall be listed in line list format, showing extent and thickness. Process Pamp。ID39。s should show anticipated extent of acoustic insulation. The Plant Insulation Specification shall include a section relating to acoustic insulation, defining the overall thicknesses and materials of construction called up in the acoustic insulation schedule. The second report stage shall be towards the end of detailed design. It shall be issued for review by Owner in time for possible changes requested by Owner to be incorporated before construction begins. For this reporting stage, the noise design shall have been pleted. The reports and schedules shall include supplier noise data for individual equipment and any acoustic treatment required. The noise plans shall show anticipated noise levels in each area. Pipework acoustic insulation requirements shall be listed in line list format, showing extent and thickness. Process Pamp。ID39。s shall show extent of acoustic insulation. The Plant Insulation Specification shall include a section relating to acoustic insulation, defining the overall thicknesses and materials of construction called up in the acoustic insulation schedule. ACCEPTANCE TESTING Noise level survey measurements will be made inside the plant areas to confirm that the noise level requirements have been satisfied. These measurements may be made at any accessible position 1m or more from any equipment during normal operations of the plant at or near its full design capacity. Additi
點擊復(fù)制文檔內(nèi)容
范文總結(jié)相關(guān)推薦
文庫吧 www.dybbs8.com
備案圖片鄂ICP備17016276號-1