【正文】
to the ground to prevent accidents. (Note 3) a motor to the inverter output terminals. Do not connect the supply line to them. Otherwise, the inverter will be damaged. (Note 4)Options a dynamic brake resistor.(Note 5) a DC reactor DCL.(Note 6)3 Terminal blocks(1)Main circuit terminal block R, S and TConnect AC power to these terminals. (Do not supply 400V to the 200V type inverter.) Terminal 1 and 2Connect the wires of the optional DC reactor DCL to these terminals. These terminals are short circuited before shipment. Terminal 2 and BConnect the optional dynamic braking (DB) resistor to these terminals. Terminal 2 and 0Connect the optional DB unit and resistor to these terminals.(2)Control terminal blockSafety PrecautionTerminals 10 and 34 carry 0V of the control circuit. Never connect these terminals to GND.4 devices and wire sizes Selection of I/O devices and precautions for main circuit wiring. The following shows the I/O devices of the VF61 unit and their wire sizes.200V typeVF61__ __ __ 22Type2R222Applicable motor (HP)Input MCCB(Note 1)Peripheral deviceInput MC (Note 2)Output MCInput side (Note 3)Wire size (mm178。)Output side (Note4)DCL terminals(1 amp。 2)315AK20K203R722520AK20K205R52230AK35K257R5221040AK50K351411221560AK65K501415222060AK65K652214222230100AK95K95222238302240125AK125K125383838372250150AK150K150383850452260225AK220K220606080552275300AK300K30080801007522100400AK400K3001501001509022130400AK400K400150150200400V typeVF61__ __ __ 44Type2R244Applicable motor (HP)Input MCCB(Note 1)Peripheral deviceInput MC (Note 2)Output MCInput side (Note 3)Wire size (mm178。)Output side(Note 4)DCL terminals(1 amp。 2)315AK20K203R744510AK20K205R54415AK20K207R5441030AK25K2011441550AK35K2515442050AK50K5022443075AK50K501430444075AK80K80141422374450100AK95K95142238454460100AK100K95223838554475125AK125K1253838607544100200AK180K150608010011044150300AK300K2208015020016044200400AK400K30015015025020044250500AK600K40020015025025044300600AK600K600250250150 (x2)Notes: values of the input MCB show the rated currents. (Determine the breaking capacity from the source capacity, etc.) shown values are those of the electromagnetic contactors MSK series made by Mitsubishi Electric Corp. wire sizes between the MCB and inverter input terminals are the sizes of the KIV or RD wires. cable length between the inverter and motor should be less than 30 meters. The shown values are those of the CV cables. the input MC is used, the interval between turning on and off should be more than 10 minutes.Safety Precautions the motor has a phase advancing capacitor, be sure to disconnect it. (If the inverter runs with the phase advancing capacitor connected, the inverter may be broken.) sure to connect a circuit breaker (input MCB) on the inverter input side. sure to connect the inverter and motor to ground. (Use the exclusive grounding terminal.)52.How to use console and Keys on ConsoleThe console has 16 columns x 4 lines LCD and operation keys as shown below.This mark designatesthat the console isselected to the numericentry key mode.LCDMode selector keysSelect the operation, function or monitor mode withthe OPR, FUNC, or MONIkey. (For details of thesemodes, see the followingsection.)^(Every press of keyalternates thesefunctions.Numeric entry keys(Upper)Function entry keys(Lower)Data setting keyReset key)Operation selectionkeys and operation keys. Monitor mode Press the MONI key, and the current setting is displayed as shown below. A monitor code (of 16 codes) and operation condition are displayed. (See for displayed items) Indicates selected operation keys. * MONITOR *REM/STOP/FOR/JOG (00)FOUT [Hz]Indicates a monitor code and its content.To change a displayed monitor code, press anumeric key (09), function entry key, and upor down arrow keys.Stored data (previous data) is displayed.After operation starts, an operation value isdisplayed. Displayed code list (Items selectable in monitor mode)Display on LCD000102030405FoutFrefIoutVoutTorq outVdcItemsOutput frequencySet frequencyOutput currentOutput voltageTorque (Torque current)DC voltageUnitsHzHzAV%VActual revolution is displayed in ASRoperation. Revolution converted fromfrequency is displayed in otheroperations.OL counter begins to count whencurrent exceeds rated motor current.OL operation starts at 100%. (OLset=100%)Estimated torque is displayed inpercentageRemarked06Motor speedMotor (synchronous) revolutionrpm07OL counterOL counter%08Line speedLine speed...6Display on LCD09101112131411term check12term check0term checkItemsInput terminal check 1Input terminal check 2Output terminalUnitsbitbitbitRemarked1 is displayed when terminal block isturned on. For meaning of each bit, setable below.DittoDitto15ROM VersionROM VersionXX