2025-05-30 03:24 本頁面
 

【文章內容簡介】 Pjs = KxPe =42=Qjs = 0= 0 kW (7)水泵 Kx = Cosφ = tgφ = Pe = 4= Pjs = = Qjs = = kW (8)平板振動器 Kx = Cosφ = tgφ = Pe = 4= Pjs = = Qjs = = (9)鋼筋切斷機 Kx = Cosφ = tgφ = Pe = 2=11 kW Pjs = KxPe =11 =Qjs = = kW(10)鋼筋彎曲機 Kx = Cosφ = tgφ = Pe = 2= kW Pjs = = kWQjs = = kW(11)、數控立式鋼筋彎曲中心 Kx = Cosφ = tgφ = Pe = 421=42 kW Pjs = 42= Qjs = = kW (12)現場照明 Kx = Cosφ = tgφ = Pe = 301=60kW Pjs = 30= 9kWQjs = 9= kW (13)辦公區(qū)用電 Kx = Cosφ = tgφ = Pe = 251=25 kW Pjs = 25=Qjs = = kW (14)生活區(qū)用電 Kx = Cosφ = tgφ = Pe = 601=60kW Pjs = 60= 18kWQjs = 18= kW 總的計算負荷計算,總箱同期系數取 Kx = 總的有功功率 Pjs = KxΣPjs = (40++ 30+++++++++9++18) =總的無功功率Qjs = KxΣQjs =(30++++2++++ ++++) = kVA 總的視在功率 Sjs =√(Pjs 178。+Qjs178。) = √(178。+178。) = 總的電流計算Ijs = Sjs/(Ue) = () = A變壓器可承載多大負載KVACOSΦ=315KVA=252 KW變壓器總的容量為315 kVA,最大可承載252 KW負載,小于變壓器最大承載負荷,選擇三相電力變壓器,它的容量能夠滿足施工使用要求。七、導線選擇總箱進線導線為:銅芯聚氯乙烯絕緣電纜線VV3*50+2*25;八、箱體的選擇本工程所有的總箱、分配箱、開關箱均采用建筑協(xié)會及安監(jiān)站推薦、公司安保部許可,符合JGJ462005“施工現場臨時用電安全技術規(guī)范”規(guī)定。九、安全用電技術措施(一)基本要求電工必須經過專業(yè)安全技術培訓考核,持特種作業(yè)有效證,方準上崗操作。電工應掌握用電安全基本知識和了解設備性能。遵守安全生產六大紀律。上崗前按規(guī)定穿戴好個人防護用品。停用設備應拉閘斷電,鎖好開關箱。負責保護用電設備的負荷線,保護零線(重復接地)和開關箱。移動用電設備時必須切斷電源,不準帶電作業(yè)。按規(guī)定每月對電器線路進行檢查,發(fā)現問題及時處理,并做好檢查、維修記錄。電工應懂得觸電急救常識和電器滅火知識。(二)電纜線路電纜線路采用埋地或架空敷設,嚴禁沿地面明設。在拉臨時電源時,電源均應架空。過道處須用鋼管保護,不能亂拉亂拖,防止電線被車物碾壓。電纜穿越建筑物、道路,必須加設防護套管。電纜架空敷設時,應沿墻壁或電桿設置,并用絕緣子固定,嚴禁使用金屬裸線作綁線。電纜埋地敷設采用地坪開槽,內鋪50mm厚粗砂,上蓋普通磚后回填