【正文】
特別是斷路器非全相操作,線路發(fā)生單相或二相斷線時,對于消弧線圈接地系統(tǒng),在某些條件下有可能發(fā)生串聯(lián)諧振,需加以防止。 若時,0,稱為過補償,此種狀態(tài)下,避免了由于諧振引起的中性點過電壓,得到了廣泛的應(yīng)用。圖2.2單相接地時補償電網(wǎng)的接線圖 設(shè)電網(wǎng)的電容電流為消弧線圈的電感電流為,則電網(wǎng)對電容電流的補償情況表示為: ()其中 =, ( )式中一脫諧度,一相對地電壓(正常時) 若=,則=0,稱為全補償,此種狀態(tài)時,故障點殘流最小,但系統(tǒng)將發(fā)生串聯(lián)諧振,中性點位移電壓將達到極高的數(shù)值,對系統(tǒng)運行不利,電網(wǎng)運行中,應(yīng)避免出現(xiàn)這種全補償運行方式。1.諧振接地系統(tǒng)的補償方式 如圖2.2所示,當(dāng)電力系統(tǒng)發(fā)生單相接地時,通過接地點的總電流為電感電流和全系統(tǒng)電容電流的矢量和。 中性點經(jīng)消弧線圈接地運行方式在電網(wǎng)中性點與地之間接入電感線圈后,單相接地的電容電流將得到補償。諧振發(fā)生時會造成系統(tǒng)過電壓和電壓互感器過電流,使到系統(tǒng)中弱絕緣設(shè)備發(fā)生對地閃絡(luò)和電壓互感器的高壓保險熔斷,甚至燒毀電壓互感器。但當(dāng)系統(tǒng)中出現(xiàn)某些擾動,使電壓互感器三相電磁飽和程度不同時,電網(wǎng)中性點就有較高電壓的位移電壓,也可能激發(fā)起諧波諧振過電壓。在中性點不接地系統(tǒng)中10kV母線常接有測量和監(jiān)視系統(tǒng)對地絕緣的電磁式電壓互感器。此種過電壓,可分為瞬間、間歇、穩(wěn)定三種,穩(wěn)定電弧接地過電壓是接地電弧在短間隙中穩(wěn)定燃燒引起的,它和前兩者不同的是作用時間長、可達數(shù)十分鐘,根據(jù)實測結(jié)果,這個數(shù)值對正常電氣絕緣來說應(yīng)能夠承受,但當(dāng)存在絕緣弱點時,可能發(fā)生擊穿,從而發(fā)生兩相兩點,甚至多點接地現(xiàn)象。 當(dāng)一相接地電容電流不大時,接地電弧會迅速自行熄滅,電網(wǎng)即可恢復(fù)正常運行;當(dāng)一相接地電容電流較大時,電弧不易熄滅,產(chǎn)生熄弧與重燃交替出現(xiàn)的狀態(tài)。 在以架空線路為主的電網(wǎng)中,不過數(shù)安到數(shù)十安,在以電纜線路為主的電網(wǎng)中,值可達數(shù)百安,一般說這種接地電容電流數(shù)值不會引起繼電保護動作跳閘,因此,電網(wǎng)將帶一相接地繼續(xù)運行,發(fā)生單相接地時,其它非接地相對地電壓升高到倍相電壓,A、B、C三相之間的線電壓,仍保持不變,不影響對用戶的正常供電,因此,允許故障持續(xù)運行2小時。應(yīng)用最廣泛的有3種:不接地、消弧線圈接地和小電阻接地。所建變電站lOkV中性點均為經(jīng)小電阻接地方式或經(jīng)消弧線圈地方式口。經(jīng)過多年的運行表明:中性點經(jīng)小電阻接地方式的10kV城區(qū)電網(wǎng)在一定程度上限制了內(nèi)部過電壓水平,從而減輕了對設(shè)備絕緣,特別是進口設(shè)備絕緣的威脅,并對一些接地故障能迅速切除。山東省城市l(wèi)OkV配電網(wǎng)系統(tǒng)中性點,在市中心和市區(qū)的110kV變電站幾乎全部采用經(jīng)自動跟蹤消弧線圈接地方式。南安供電局認(rèn)為lOkV城市電網(wǎng)中性點經(jīng)電阻接地運行方式存在較多的問題,比較后認(rèn)為弊大于利。南安小電阻接地系統(tǒng)的運行方式先后發(fā)生多起因鑄鐵電阻熱容量不夠,單相接地過渡電阻的影響及整定值偏大導(dǎo)致電阻柜燒毀事故。南安市的lOkV城市電網(wǎng)中性點接地方式的變更有力地支持這一觀點。 選擇配電網(wǎng)中性點接地方式,應(yīng)根據(jù)各地電網(wǎng)結(jié)構(gòu)、電容電流水平,電纜化程度,負(fù)荷重要程度等實際情況進行結(jié)合經(jīng)濟技術(shù)比較后決定,最重要的指標(biāo)是電容電流水平,當(dāng)接地故障電容電流較大時,一般采用中性點經(jīng)消弧線圈接地或經(jīng)電阻接地,這一觀點各地供電局基本形成共識,但究竟是采用中性點經(jīng)消弧線圈有利,還是采用中性點經(jīng)電阻接地更好,卻有很大的爭議。 Arc suppression coil目 錄摘要 ⅠAbstract Ⅰ目 錄 Ⅱ1 緒論 32 10kV配電網(wǎng)中性點接地運行方式 5 中性點不接地方式 5 中性點經(jīng)消弧線圈接地運行方式 7 中性點經(jīng)小電阻接地運行方式 93 南安市區(qū)10kV配電網(wǎng)現(xiàn)狀 18 南安市區(qū)電網(wǎng)現(xiàn)況 193.1.1 南安市地理情況 19 南安市區(qū)主網(wǎng)現(xiàn)狀 19 南安市區(qū)10kV配電網(wǎng)現(xiàn)狀 19 電容電流測量 203.2.1 測試方法 20 測試條件 20 測量結(jié)果 21 測量結(jié)果分析 22 南安市區(qū)10kV配電網(wǎng)中性點接地方式的現(xiàn)狀 234 南安市區(qū)10kY配電網(wǎng)中性點接地方式的選擇 25 南安市區(qū)10kV配電網(wǎng)中性點接地方式的選擇 25 小電阻接地方式的優(yōu)化 26 南安沿海地區(qū)10kV配電網(wǎng)中性點接地方式的選擇 28 南安沿海地區(qū)10kV配電網(wǎng)中性點接地方式的選擇 284.2.2 新型的中性點補償接地方式 29參考文獻 33致謝 351 緒論 問題的提出 電力系統(tǒng)的中性點接地方式是一個綜合性的技術(shù)問題,它與系統(tǒng)的供電可靠性、人身安全、設(shè)備安全、絕緣水平、過電壓保護、繼電保護、通訊干擾(電磁干擾)以及接地裝置等問題有密切關(guān)系。關(guān)鍵詞:10kV電網(wǎng);中性點接地方式;小電阻;消弧線圈AbstractThis paper is aimed at nanan district lOkV distribution network neutral point grounding way choice question for study. Paper first for 10 kv distribution network neutral point operation of a variety of ways to carry on the analysis, pare the characteristics of all kinds of operation mode, and then to conduct a prehensive investigation about the present situation of nanan district lOkV distribution network, and the actual measurement for each substation lOkV busbar capacitance current to, as the basis for correct selection of neutral point grounding way to provide accurate information. Paper also for Southampton region is currently using the small resistance grounding mode of summarized, bining with the actual running effect their advantages and disadvantages are put forward, and the problems existed in further improving measures are put forward. Through indepth survey of nanan district 10 kv power distribution network, research and test, it is concluded that nanan city, officer, bridge, water head and ishii lOkV distribution network can continue to use small resistance grounding mode, the south north lOkV distribution network using the conclusion of arc suppression coil grounding way better.Key words: 10 kv power grid, Neutral point grounding way。論文還對南安地區(qū)目前正在采用的小電阻接地方式進行總結(jié),結(jié)合實際運行效果提出其優(yōu)缺點,并對其存在問題提出了進一步的改進措施。題目 南安電網(wǎng)10kV配電網(wǎng)中性點運行方式分析 專 業(yè):電氣工程及其自動化學(xué) 院: 電氣工程學(xué)院 年 級: 學(xué)習(xí)形式: 學(xué) 號: 論文作者: 指導(dǎo)教師: 職 稱: XXX學(xué)院 制完成時間: 摘要本論文就是針對南安地區(qū)lOkV配電網(wǎng)中性點接地方式的選擇問題進行研究。論文首先對10kV配電網(wǎng)中性點運行的各種方式進行分析,比較各種運行方式的特點,然后對南安地區(qū)lOkV配電網(wǎng)現(xiàn)狀進行全面的調(diào)研,并對各變電站lOkV母線電容電流進行實際測量,為正確選擇中性點接地方式提供準(zhǔn)確的基礎(chǔ)資料。通過對南安地區(qū)10kV配電網(wǎng)的深入調(diào)查、研究、試驗,得出南安市區(qū)、官橋、水頭及石井lOkV配電網(wǎng)可以繼續(xù)采用小電阻接地方式,而南安北區(qū)lOkV配電網(wǎng)采用消弧線圈接地方式更好的結(jié)論。 Small resistance。中性點接地方式的正確選擇及其在不同條件下的實旋具有越來越重要的意義。廈門供電局的要煥年高級工程師就極力反對10kV城市電網(wǎng)中性點采用小電阻接地方式,而是推薦消弧線圈接地方式,他認(rèn)為:采用小電阻接地方式,人為地增加了接地故障電流,對人身安全、設(shè)備安全、通信干擾帶來了不少問題和麻煩,特別是新型消弧線圈技術(shù)有了較大的發(fā)展,微機接地保護在不增大故障電流的條件下,照樣可以有選擇性地跳開故障線路,更顯示了諧振接地方式的優(yōu)勢。南安于1993年開始將原來所有消弧線圈接地的lOkV城市電網(wǎng)改為小電阻接地的運行方式,經(jīng)過幾年的運行,發(fā)現(xiàn)線路和跳閘次數(shù)太多,最多一天跳閘4次,重合不成功,強送成功,或強送不成功,查不到故障點,再強送成功。另外,發(fā)現(xiàn)中性點經(jīng)電阻接地的10kV電網(wǎng)對有些接地故障不能及時跳閘,從而危及人身安全。由于將中性點經(jīng)電阻接地運行方式全部又改為經(jīng)消弧線圈接地方式具有相當(dāng)大難度,因此南安供電局現(xiàn)在繼續(xù)維持經(jīng)電阻接地的運行方式,而將新投lOkV城市電網(wǎng)中性點接地方式改為經(jīng)消弧線圈接地的運行方式。另一方面,廣州、上海、北京、合肥許多火城市的lOkV城區(qū)電網(wǎng)己將原來中性點不接地或經(jīng)消弧線圈接地方式改為經(jīng)小電阻接地的運行方式。南安市l(wèi)OkV電網(wǎng)中性點接地方式既采用小電阻接地又采用消弧線圈接地,到2004年10月,南安供電局已投運的變電站共裝設(shè)lOkV中性點接地系統(tǒng)213套,其中經(jīng)小電阻接地方式有122套,經(jīng)消弧線圈接地有91套,有9個變電站未裝設(shè)中性點接地系統(tǒng),屬于不接地方式。