【正文】
取貯水池容積為45立方米。 根據(jù)上述計算算出最高日用水量和最大時用水量:Qd=Qh= 地下室貯水池容積和屋頂水箱容積計算根據(jù)《建筑給水排水設(shè)計規(guī)范》(GB500152003),貯水池的有效容積應(yīng)按進水量和用水量變化曲線經(jīng)計算確定,當資料不足時,宜按最高日用水量的20%~25%確定。 ─洗衣房工作時間,取為8h。 ─每公斤干衣耗水量,L/kg。, (24)式中 ─洗衣房的日用水量,L/d。則用水量為 (2)辦公樓人數(shù)按倒班樓人數(shù)的8%計,共56人。根據(jù)式(21)、(22)計算最高日用水量和最高日最大時用水量。d)。 最高日用水量和最高日最大時用水量根據(jù)用水定額和本建筑的用水單位數(shù)計算最高日用水量和最高日最大時用水量,最高日用水量計算公式為: (21) 式中 Qd —最高日用水量,L/d; m—用水單位數(shù),人或床位數(shù); qd —最高日用水定額,L/(人 建筑內(nèi)部給水系統(tǒng)設(shè)計計算 給水用水定額和時變化系數(shù)根據(jù)《建筑給水排水設(shè)計規(guī)范》(GB500152003)【1】,Ⅰ類、Ⅱ類宿舍生活用水定額為每人每日150~200L,~;辦公樓用水定額每人每班為 30~50L,~;洗衣房的用水定額為每千克干衣40~80L,~;停車庫地面沖洗用水定額為每平方米每次2~3L。根據(jù)規(guī)范要求和建筑特點,給水系統(tǒng)采用水泵水箱聯(lián)合分區(qū)供水,地下3層到4層為Ⅰ區(qū),倒班樓5到14層為Ⅱ區(qū),15到24層為Ⅲ區(qū),25到30層為Ⅳ區(qū);辦公樓5到13層為Ⅱ區(qū),14到19層為Ⅲ區(qū),20到26層為Ⅳ區(qū)。低區(qū)由市政管網(wǎng)直接供水,高區(qū)由屋頂水箱供水。,。自噴系統(tǒng)采用濕式自噴系統(tǒng)。消防系統(tǒng):消火栓系統(tǒng)和自噴系統(tǒng)均采用臨高壓給水系統(tǒng),分區(qū)給水。雨水系統(tǒng):為了建筑美觀,采用重力式排水系統(tǒng)。Ⅰ區(qū)由市政水壓直接供水,Ⅱ、Ⅲ、Ⅳ區(qū)由高位水箱減壓供水。防火設(shè)計為一類建筑,耐火等級為一級。熱水供應(yīng)系統(tǒng)采用全循環(huán)方式,水加熱器放在地下三層設(shè)備間內(nèi)。雨水系統(tǒng)采用內(nèi)排水系統(tǒng)。Ⅰ區(qū)由市政水壓直接供水,Ⅱ,Ⅲ,Ⅳ區(qū)由高位水箱減壓供水。本次設(shè)計主要包括給水系統(tǒng),排水系統(tǒng),雨水系統(tǒng),熱水供應(yīng)系統(tǒng),消火栓給水系統(tǒng)以及自動噴水滅火系統(tǒng)。畢 業(yè) 設(shè) 計設(shè)計題目某綜合樓建筑給水排水工程設(shè)計方案二 學(xué)生姓名 吳雨晴 學(xué) 號 20103885 專業(yè)班級 給水排水工程101班 指導(dǎo)教師 徐得潛 院系名稱 土木與水利工程學(xué)院 20 14 年 06 月 07 日目錄中文摘要 1英文摘要 21 前言 3 工程概況 3 設(shè)計任務(wù) 3 設(shè)計方法 3 設(shè)計依據(jù) 42 建筑給水系統(tǒng) 5 建筑內(nèi)部給水系統(tǒng)設(shè)計說明 5 建筑內(nèi)部給水系統(tǒng)設(shè)計計算 53 建筑排水系統(tǒng) 18 建筑內(nèi)部排水系統(tǒng)設(shè)計說明 18 建筑內(nèi)部排水系統(tǒng)設(shè)計計算 18 雨水排水系統(tǒng)設(shè)計說明 34 雨水排水系統(tǒng)設(shè)計計算 344 室內(nèi)消防給水系統(tǒng) 37 消火栓給水系統(tǒng)設(shè)計說明 37 消防池和水箱容積計算 37 消火栓給水系統(tǒng)設(shè)計計算 38 自動噴水滅火系統(tǒng)設(shè)計計算 495 建筑熱水系統(tǒng) 56 熱水供應(yīng)系統(tǒng)設(shè)計說明 56 熱水供應(yīng)系統(tǒng)設(shè)計計算 566 結(jié)束語 867 謝辭 878 參考文獻 8888 / 90某綜合樓建筑給水排水工程設(shè)計方案二摘要:本工程為一高層綜合樓,主樓裙房4層,倒班樓為5到30層,辦公樓為5到26層,地下共三層,內(nèi)有車庫和職工食堂。建筑占地面積6000平方米,總建筑面積97566平方米,為一類高層建筑。給水系統(tǒng)采用水池水泵水箱聯(lián)合供水方式,分四個區(qū),地下3層到4層為Ⅰ區(qū),倒班樓5到14層為Ⅱ區(qū),15到24層為Ⅲ區(qū),25到30 層為Ⅳ區(qū);辦公樓5到13層為Ⅱ區(qū),14到19層為Ⅲ區(qū),20到26層為Ⅳ區(qū)。排水采用污廢合流體制,廚房污水單獨收集經(jīng)隔油池后排至市政污水管網(wǎng)。消防系統(tǒng)包括消火栓系統(tǒng)和自動噴水滅火系統(tǒng),采用臨高壓給水系統(tǒng),火災(zāi)初期10分鐘滅火用水由屋頂高位水箱提供,后期由水泵提供。關(guān)鍵詞:綜合樓 給水系統(tǒng) 排水系統(tǒng) 消防系統(tǒng) 熱水系統(tǒng) 設(shè)計Option two of a plex building water supply and drainage engineering designAbstract: The project is a highrise plex building. The podium of the main building has four layers,five to thirty layers for shifts building,five to twentysix layers for office building. The height of the aerial parts of the building is meters, and the height of the underground part of the building is meters. Underground section is divided into three floors, there are garage and cafeteria in building covers an area of 6000 square meters,the total construction area is 97566 square is type one highrise design mainly includes the water supply system, drainage system, rainwater system, hot water supply system, fire hydrant water supply system and automatic sprinkler system. Feedwater is supplied jointly by the pool, pump and tank in water supply system. The system is divided into four regions, of which the region I is underground 3 to 4 floor, The shifts building’s region II is 5 to 14 floor, region III is 15 to 24 floor, region IV is 25 to 30 floor. The office building’s region II is 5 to 13 floor, region III is 14 to 19 floor, region IV is 20 to 26 floor. Region I is supplied by the municipal water directly. region II, III, IV use high water tank to relax the pressure. Sewage and waste interflow system is used in drainage option,and kitchen sewage collected separately flows to the municipal sewage pipe network after it goes through grease trap. Rainwater system uses internal drainage system. Fire protection system includes fire hydrant system and automatic sprinkler system, using temporary high pressure water supply system, and water to extinguish fire is supplied by the roof water tank in the initial 10 minutes, and then provided by the pump . Hot water supply system adopts full cycle mode, and water heater is placed in the basement.Keywords:plex building water supply system drainage system fire protection system hot water supply system design1 前言 工程概況本建筑為一高層綜合樓,主樓裙房4層,倒班樓為5到30層,辦公樓為5到26層,地下共三層,地下3 層為車庫和水池及泵房,地下1層為車庫及廚房。 設(shè)計任務(wù)本次設(shè)計任務(wù)如下:1. 建筑內(nèi)部給水系統(tǒng)設(shè)計2. 建筑排水系統(tǒng)設(shè)計(1)建筑內(nèi)部排水系統(tǒng)設(shè)計(2)建筑屋面雨水排水系統(tǒng)設(shè)計 3. 熱水供應(yīng)系統(tǒng)設(shè)計4. 室內(nèi)消防系統(tǒng)設(shè)計(1)消火栓系統(tǒng)設(shè)計(2)自動噴水滅火系統(tǒng)設(shè)計 設(shè)計方法根據(jù)建筑特點和相關(guān)設(shè)計規(guī)范,本次設(shè)計采用如下方案:給水系統(tǒng):采用水池水箱水泵聯(lián)合供水,分四個區(qū),倒班樓5到14層為Ⅱ區(qū),15到24層為Ⅲ區(qū),25到30層為Ⅳ區(qū);辦公樓5到13層為Ⅱ區(qū),14到19層為Ⅲ區(qū),20到26層為Ⅳ區(qū)。排水系統(tǒng):采用污廢合流,裙房包廂和衛(wèi)生間采用伸頂通氣,倒班樓和辦公樓設(shè)置專用通氣立管。 熱水供應(yīng)系統(tǒng):倒班樓采用全循環(huán)供水方式。消防系統(tǒng)地下3層到4層為Ⅰ區(qū),倒班樓5到14層為Ⅰ區(qū),15到30層為Ⅱ區(qū);辦公樓5到13層為Ⅰ區(qū),14到26層為Ⅱ區(qū)。 設(shè)計依據(jù)、建筑用途(1)建筑給水排水設(shè)計規(guī)范(GB500152003),2009 版(2)高層民用建筑設(shè)計防火規(guī)范(GB5004595),2005 年版(3)自動噴水滅火系統(tǒng)設(shè)計規(guī)范(GB500842001),2005 年版(4)建筑設(shè)計防火規(guī)范(GB500162006)(5)給水排水制圖標準(GB/T501062001)2 建筑給水系統(tǒng) 建筑內(nèi)部給水系統(tǒng)設(shè)計說明本建筑以城市給水管網(wǎng)作為水源,由DN100的兩根引入管引入建筑內(nèi)。該建筑層數(shù)多,豎向高度大,市政給水管網(wǎng)不能直接供應(yīng)高區(qū)給水,為避免建筑低層配水點靜水壓力過大,需要進行給水分區(qū)。根據(jù)《建筑給水排水設(shè)計規(guī)范》(GB500152003),2009 條規(guī)定,豎向分區(qū)應(yīng)符合下列要求:(1),;(2)(或配水橫管),宜設(shè)減壓或調(diào)壓設(shè)施;(3)各分區(qū)最不利配水點的水壓,應(yīng)滿足用水水壓要求。給水系統(tǒng)采用上行下給的方式,由水箱引出兩根給水管,一根提供Ⅱ、Ⅲ、Ⅳ區(qū)冷水,一根經(jīng)水加熱器供應(yīng)倒班樓Ⅱ、Ⅲ、Ⅳ區(qū)熱水。根據(jù)本建筑物的性質(zhì)和室內(nèi)衛(wèi)生設(shè)備的完善程度,確定各部分最高日用水定額及時變化系數(shù)如下:倒班樓每人每天200L,,使用時間按24小時計;辦公樓每人每班40L,使用時間按8小時計;洗衣房每千克干衣40L,使用時間按8小時計;,時變化系數(shù)為 ,使用時間按8小時計。d)或 L/(床最高日最大時用水量計算公式為: (22)式中 Qh —最高日最大時用水量,L/h;T—建筑物的用水時間,h;Kh —小時變化系數(shù)。(1)本建筑倒班樓共有床位667個,近似取為700個。則用水量為 (3)地下車庫面積為8194平方米,則沖洗用水量為 (4)洗衣房用水量計算 (23)式中 ─每日洗滌量,;─每日洗滌量,(床月); ─床數(shù);─洗衣房每月工作日數(shù),一般按25d計。 ─洗衣房的日用水量,kg/d