【正文】
1011 2 4 4 / / 32 1112 2 4 4 1 / 32 1213 2 4 4 1 / 32 1314 4 12 12 2 4 50 1415 6 16 16 3 4 50 1516 8 28 28 4 12 70 1617 10 32 32 5 12 70 1718 11 36 36 6 12 70 最不利點為 0點 . 低區(qū)給水系統(tǒng)壓力校核 低區(qū)生活給水系統(tǒng)所需壓力按下式計算: 4321 HHHHH ???? (16) 式中 H給水系統(tǒng)所需要的水壓, kPa; H1克服幾何給水高度所需要的供水壓力, kPa; 內(nèi)蒙古工業(yè)大學本科畢業(yè)論文 15 H2管路沿程水頭損失和局部水頭損失, kPa; H3水流經(jīng)過水表時的水頭損失, kPa; H4配水最不利點所需的流出水頭, kPa。 . 低區(qū)生活給水管網(wǎng)水力計算 低區(qū)地下 2~ 6 層計算用圖如圖 1圖 1圖 1圖 14 所示。對本綜合樓采用變頻調(diào)速并聯(lián)給水方案來講,低區(qū)給水系統(tǒng)需要復合室外管網(wǎng)提供的水壓是否滿足低區(qū)給水系統(tǒng)所需壓力;中、高區(qū)給水系統(tǒng)需要確定水泵的流量和揚程,為選擇水泵提供依據(jù)。 每條引入管水表前均應裝設倒流防止器,以防壓力表 型 正常用水時 消 防 時 旋翼式 螺翼式 內(nèi)蒙古工業(yè)大學本科畢業(yè)論文 10 不足時回流污染。水流經(jīng)過水表的水頭損失為: 平時: k P ak P aq qH gB 222m a x2 ???? ,符合設計要求。并應校核水表通過設計流量時,其水頭損失應滿足表 12 規(guī)定。 . 水表的選擇 ( 1)設計計算依據(jù) 水表的選擇包括確定水表的類型及口徑,水表的類型應根據(jù)水表的特性和通過水表的水質(zhì)、水量、水溫、水壓等情況選定。 則生活引入管道的設計流量為 hm 33 7 .5 .0 8 ??? 本設計采用室外生活管道和消防管道共用系統(tǒng),引入管管徑設計按建筑生活用水量達到最大時流量時,應仍能保證室內(nèi)、外消防用水量確定。 ( 2)引入管設計流量的確定 本設計符合上述第 3 條 所述的情況,引入管的設計流量應為低區(qū)生活用水設計秒流量和中、高區(qū)貯水池設計補水量的疊加。設計補水量不宜大于建筑物最高日最大時生活用水量,且不得小于建筑物最高日平均時生活用水量。 . 引入管設計流量的確定 ( 1)設計計算依據(jù) 摘自《建筑給水排水設計規(guī)范》 (GB500152020) 建筑物的給水引入管的設計流量,符合下列要求: 1 當建筑物內(nèi)的生活用水全部由室外管網(wǎng)直接供水時,取建筑物內(nèi)的生活用水設計秒流量。此時,可以采用建筑日用水量的百分數(shù)估算生活貯水量,通??扇∪沼盟康膬?nèi)蒙古工業(yè)大學本科畢業(yè)論文 8 20%~ 25%,最大不得大于 48h 的用水量。 ( 1)設計計算依據(jù) 貯水池的生活調(diào)節(jié)容積可按下式計算: ? ? bgby TV ?? (13) ? ? tgbgb TQT ?? (14) 式中 Vy貯水池有效容積, m3; Qb水泵的出水量, m3/h; Qg水池的進水量, m3/h; Tb水泵運行時間, h; Tt水泵運行時間間隔, h。 貯水池的容積應根據(jù)用水對象的要求,結合市政供水的可靠程度確定。根據(jù)圖紙資料,經(jīng)計算,確定這些場所的人口數(shù)約為 3382 人; 內(nèi)蒙古工業(yè)大學本科畢業(yè)論文 7 ( 2) 商場面積約為 1300 m2; 表 11 用水量計算表 序號 名稱 用水單位數(shù) 用水定額 最大日用水量 Qd(L/d) Kh 最大時用水量 Qh(L/h) 用水時間 T(h) 1 辦公室 3382 人 /班 40L/(人 .班 ) 135280 18939 10 2 商場 1300m2 6L/m2 7800 910 12 合計 143080 19849 mQd ?? hmQ / 3h ? . 水池、水表的計算 . 水池的計算 高層建筑的生活給水系統(tǒng),應能充分、安全、可靠地保證生活用水 。 . 設計計算 根據(jù)設計原始資料、建筑性質(zhì)和衛(wèi)生器具設置完善程度,依據(jù)《建筑給水排水設計規(guī)范》 (GB500152020),本綜合樓用水量標準及用水量見表 11。 dd mqQ ? (11) TQKQ dhh? (12) 式中 Qd最高日用水量, L/d; m用水單位數(shù),人或床位數(shù)等,工業(yè)企業(yè)建筑為每班人數(shù); qd最高日生活用水定額, L/(人 .d)、 L/(床 .d)或 L/(人 .班 ); Qh最大小時用水量, L/h; Kh小時變化系數(shù); T建筑物的用水時間,工業(yè)企業(yè)建筑為每班用水時間, h。它的選用是否恰當、合理,對給水系統(tǒng)的建設投資和運行使用都有很大影響。 通過設計應熟悉和了解建筑給排水工程的一般設計原則、步驟與方法,了解建筑給水排水方案比較的原則和方法,掌握冷水、熱水、消防給水、排水計算方法以及設計說明書的編寫和施工圖設計與繪制的方法。因此,正確設計建筑給水排水工程有重大社會意義和經(jīng)濟意義。 建筑給水排水工程是城市建設中重要的基礎設施項目。通過畢業(yè)設計訓練學生綜合應用所學基礎課和專業(yè)基礎課知識。 內(nèi)蒙古工業(yè)大學本科畢業(yè)論文 2 Abstract This building is the largescale prehensive building, is located in the centre of Hohhot , the construction is highly , total floor space approximately 35,000 square meters. This building possesses for water draining water presses the highrise construction to request for draining water to carry on the design. Unifies the actual situation, according to the building nature, the use, is equipped with the consummation with the room in for the water draining water sanitary equipment, concrete gives the drainage system design to be as follows: Water supply system: This construction underground to ground six by outdoor municipal administration pipe work direct water supply, the water supply system of seven to twentyfour is the water pump、 the roof water tank and the reducing value joins. supposed two leadin tubes. From different direction introduction. Both has safeguarded the water supply security, and saved the energy consumption. Drainage system: This design uses the dirt waste water parting emissions system. The tubing used had the shock resistance cast iron pipe waste. might further improve the environment quality for this. In the basement nearby the fire electricity stairwell, the pump house ground are equipped with the sump and the waste water lifting gear. Fire prevention system: This building fire protection rank belongs to the dangerous levelⅡ The level, the design content including the fire hydrant system and sprays automatically system. In supposes the experimental fire hydrant installment in the roof water tank between, the fire hydrant service pipe assumes the ringlike arrangement。 各系統(tǒng)中的立管設在管井內(nèi)或沿墻敷設,水平管根據(jù)各系統(tǒng)的特點明敷或暗敷。在屋頂水箱間內(nèi)設實驗用消火栓裝置,消火栓給水管網(wǎng)呈環(huán)狀布置,各消火栓箱內(nèi)設消防水泵啟動電鈕,能直接啟動消防泵;室外設地下式水泵結合器,保證消防安全可靠。地下室內(nèi)消防電梯井旁、泵房地面均設有集水坑和廢水提升裝置。 排水系統(tǒng): 本設計采用污廢水分流排放體 制。結合實際情況,根據(jù)建筑物的性質(zhì),用途,和室內(nèi)設有完善的給水排水衛(wèi)生設備,具體的給排水系統(tǒng)設計如下: 給水系統(tǒng): 本建筑地下二層至地上六層由室外市政管網(wǎng)直接供水,七至二十四層采用水泵、屋頂水箱和減壓閥相接合的給水方式;設兩條引入管,從不同的方向引入。內(nèi)蒙古工業(yè)大學本科畢業(yè)論文 1 大型綜合樓給水排水消防系統(tǒng)設計 摘 要 該建筑為大型綜合樓,位于呼和浩特市中心,建筑高度為 米,總建筑面積約 萬平方米。本建筑物所有給水排水均按高層建筑給排水要求進行設計。既保障了供水安全,又節(jié)約了能耗。管材采用了具有抗震功能的排水鑄鐵管,為此可進一步提高環(huán)境質(zhì)量。 消防系統(tǒng): 該建筑防火等級屬于中危險級Ⅱ級,設計內(nèi)容包括消火栓系統(tǒng)和自動噴淋系統(tǒng)。走廊,辦公間,電梯前室設閉式自動噴淋系統(tǒng),自動扶梯旁的防火卷簾處設置水幕系統(tǒng)。 關鍵詞: 給水;排水;消火栓;自動噴淋。 Room peripheral equation below water pump coupler, guarantee fire prevention safe reliable. The corridor, the work, in front of the elevator the room supposes the closed type to spray the system automatically. The system of vertical pipe in pipe or along the wall of pipe laying, level according to the system characteristics that apply or concealed. Key word: for water ; Draining off water ; The fire hydrant ; Spurting voluntarily pours . 內(nèi)蒙古工業(yè)大學本科畢業(yè)論文 3 目錄 引 言 ...................................................................................................................... 5 設計計算說明書 ........................................................................................................ 6 1. 給水系統(tǒng)計算 ........................................................................................