【正文】
子顯熱散熱量,W,見《空氣調(diào)節(jié)》課本表216 φ, n—同上式查《空氣調(diào)節(jié)》課本表216可知,t=26℃時(shí), q2=105W故人體潛熱散熱形成的冷負(fù)荷一樓和二樓負(fù)荷計(jì)算及匯總詳見下表:建筑物的冷負(fù)荷計(jì)算表及各項(xiàng)冷負(fù)荷詳表:時(shí)間15:0016:0017:0018:0019:00建筑物面積(㎡)夏季總冷負(fù)荷最大時(shí)刻(含新風(fēng)/全熱)(h)17:0017:0017:0017:0017:00夏季室內(nèi)冷負(fù)荷最大時(shí)刻(全熱)(h)17:0017:0017:0017:0017:00夏季總冷負(fù)荷(含新風(fēng)/全熱)(W)13778611380189138210613791381364425夏季室內(nèi)冷負(fù)荷(全熱)(W)816671819000820917817948803235夏季總濕負(fù)荷(含新風(fēng))(kg/h)夏季室內(nèi)濕負(fù)荷(kg/h)夏季新風(fēng)量(m^3)夏季新風(fēng)冷負(fù)荷(W)561190561190561190561190561190夏季新風(fēng)機(jī)組冷負(fù)荷(全熱)(W)561190561190561190561190561190夏季新風(fēng)機(jī)組冷負(fù)荷(顯熱)(W)155061155061155061155061155061夏季新風(fēng)機(jī)組冷負(fù)荷(潛熱)(W)406128406128406128406128406128各樓層的冷負(fù)荷計(jì)算表及樓層冷負(fù)荷詳表:時(shí)間15:0016:0017:0018:0019:001樓層面積(㎡)夏季總冷負(fù)荷最大時(shí)刻(含新風(fēng)/全熱)(h)17:0017:0017:0017:0017:00夏季室內(nèi)冷負(fù)荷最大時(shí)刻(全熱)(h)17:0017:0017:0017:0017:00夏季總冷負(fù)荷(含新風(fēng)/全熱)(W)688931690095691053689569682212夏季室內(nèi)冷負(fù)荷(全熱)(W)408336409500410458408974401618夏季總濕負(fù)荷(含新風(fēng))(kg/h)夏季室內(nèi)濕負(fù)荷(kg/h)夏季新風(fēng)量(m^3)夏季新風(fēng)冷負(fù)荷(W)280595280595280595280595280595夏季新風(fēng)機(jī)組冷負(fù)荷(全熱)(W)280595280595280595280595280595夏季新風(fēng)機(jī)組冷負(fù)荷(顯熱)(W)7753177531775317753177531夏季新風(fēng)機(jī)組冷負(fù)荷(潛熱)(W)2030642030642030642030642030642樓層面積(㎡)夏季總冷負(fù)荷最大時(shí)刻(含新風(fēng)/全熱)(h)17:0017:0017:0017:0017:00夏季室內(nèi)冷負(fù)荷最大時(shí)刻(全熱)(h)17:0017:0017:0017:0017:00夏季總冷負(fù)荷(含新風(fēng)/全熱)(W)688931690095691053689569682212夏季室內(nèi)冷負(fù)荷(全熱)(W)408336409500410458408974401618夏季總濕負(fù)荷(含新風(fēng))(kg/h)夏季室內(nèi)濕負(fù)荷(kg/h)夏季新風(fēng)量(m^3)夏季新風(fēng)冷負(fù)荷(W)280595280595280595280595280595夏季新風(fēng)機(jī)組冷負(fù)荷(全熱)(W)280595280595280595280595280595夏季新風(fēng)機(jī)組冷負(fù)荷(顯熱)(W)7753177531775317753177531夏季新風(fēng)機(jī)組冷負(fù)荷(潛熱)(W)203064203064203064203064203064河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 空調(diào)方案確定和經(jīng)濟(jì)技術(shù)分析4 空調(diào)方案確定和經(jīng)濟(jì)技術(shù)分析空氣調(diào)節(jié)系統(tǒng)一般由空氣處理設(shè)備和空氣輸送管道以及空氣分配裝置所組成,根據(jù)需要,它有多種不同形式。本設(shè)計(jì)不采用各系統(tǒng)冷負(fù)荷綜合最大值作為制冷機(jī)的容量,而是把每個(gè)逐時(shí)值的累加最大值作為選用冷水機(jī)組的依據(jù),為使其有富裕值,一般在選用冷水機(jī)組時(shí),應(yīng)以小于1的參差系數(shù), 有關(guān)空調(diào)冷負(fù)荷的具體計(jì)算請(qǐng)見下列計(jì)算過程。設(shè)計(jì)內(nèi)容包括商場(chǎng)的一二層的集中中央空調(diào)系統(tǒng)設(shè)計(jì)和該空調(diào)系統(tǒng)配套的冷凍站設(shè)計(jì),空調(diào)水系統(tǒng)設(shè)計(jì)及風(fēng)系統(tǒng)設(shè)計(jì),空調(diào)系統(tǒng)管道保溫處理及設(shè)備減震設(shè)計(jì)。2. 防煙分區(qū)和擋煙垂壁《高規(guī)》第5. 1. 6 條“設(shè)置排煙設(shè)施的走道、凈高不超過6. 00m 的房間,應(yīng)采用擋煙垂壁、隔墻或從頂棚下突出不小于0. 50m的梁劃分防煙分區(qū)。風(fēng)機(jī)、水泵、空調(diào)器等空調(diào)設(shè)備,風(fēng)管、水管的隔震處理應(yīng)引起足夠重視。風(fēng)口的布置,要能夠適應(yīng)以后隔墻的變化和貨柜的重新組合等變化,適應(yīng)今后商場(chǎng)變化的需要。但目前國(guó)內(nèi)商場(chǎng)的衛(wèi)生條件和環(huán)境較差,一般多采用下回風(fēng)或側(cè)回風(fēng)。 百貨商場(chǎng)的空調(diào)方式百貨商場(chǎng)的空調(diào)方式大致分為集中方式和局部方式。中央空調(diào)系統(tǒng)節(jié)能措施:當(dāng)人們意識(shí)到能源危機(jī)時(shí),減少能源的消耗在社會(huì)生活中愈來愈重要。機(jī)組臺(tái)數(shù)過多有如下缺點(diǎn): 1)單機(jī)容量下降,機(jī)組COP下降,能耗高; 2)機(jī)組臺(tái)數(shù)多,配置的循環(huán)水泵也多,水泵并聯(lián)多,并聯(lián)損失高;3)機(jī)組臺(tái)數(shù)多,配置的循環(huán)水泵多,占用機(jī)房面積就大。 百貨商場(chǎng)的空調(diào)設(shè)備目前,百貨商場(chǎng)采用的冷源有以下幾種:往復(fù)式(活塞式)制冷機(jī)、離心式制冷機(jī)、螺桿式制冷機(jī)、吸收式制冷機(jī)等。幾乎需80%的排氣才能滿足衛(wèi)生要求。5)為防止從主要進(jìn)出口侵入的室外空氣,商業(yè)建筑物在冬季應(yīng)設(shè)置熱風(fēng)幕,以防止冷風(fēng)從大門侵入室內(nèi);夏季多采用普通空氣幕(又稱氣簾)。并且很多商場(chǎng)的柜臺(tái)、貨架和店鋪的開間組合,有時(shí)要 重新劃分和作重新的布置。隨著人們生活水平的提高 購買力增強(qiáng) 近年來增加了不少商業(yè)建筑,繁華地區(qū)的商場(chǎng)顧客比較擁擠。百貨商場(chǎng)除營(yíng)業(yè)大廳外,還配備有倉庫、管理、加工等用房。關(guān)鍵詞: 空調(diào)系統(tǒng) 冷水機(jī)組 諧波反應(yīng)法 風(fēng)機(jī)盤管ABSTRACT With the constant improvement of the level of national economy in our country, the construction industry continues to steadily forward, and pared the development of the construction industry a few years ago, the developers will further sights, they no longer onesided pursuit of volume rate and how to develop the more low cost, the better, but more peopleoriented, development really high fort level, building high quality residential and mercial buildings. At present, along with our country economic growth gradually, improving people39。河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 文獻(xiàn)綜述 畢 業(yè) 設(shè) 計(jì) [論 文]題 目: 廣州市某購物商城中央空調(diào)系統(tǒng)設(shè)計(jì) 學(xué) 院: 河南城建學(xué)院 專 業(yè): 熱能與動(dòng)力工程 姓 名: 學(xué) 號(hào): 指導(dǎo)老師: 完成時(shí)間: 摘 要隨著我國(guó)國(guó)民經(jīng)濟(jì)水平的不斷提高,建筑業(yè)也在持續(xù)穩(wěn)定地向前發(fā)展,和前幾年建筑業(yè)的發(fā)展相比,目前的發(fā)展商將眼光放的更遠(yuǎn),他們不再片面的追求容積率及如何將開發(fā)成本降得越低越好,而是更多的考慮以人為本,開發(fā)真正舒適度高、建筑質(zhì)量高的居住及商用建筑。s living environment fortable living conditions the demand is higher and higher, the demand for central air conditioning has bee more and more big, the central airconditioning energy saving, fortable, pay more attention to health. Therefore, design a energy saving, fortable, healthy central air conditioning engineering is of great practical significance. This design topic is one hundred shopping malls in guangzhou summer the central air conditioning system design, main task is to plete a, on the second floor of the cold load calculation。這類建筑的特點(diǎn)是:1)空間較大、柜和陳列擺設(shè)多樣、人流眾多,要合理安排顧客人流路線和貨物進(jìn)出路線,避免交錯(cuò)混雜。為了保護(hù)廣大顧客 和商場(chǎng)職工的健康,我國(guó)衛(wèi)生防疫部門對(duì)面業(yè)建筑提出了衛(wèi)生要求, 對(duì)較大的重點(diǎn)商場(chǎng)還進(jìn)行過監(jiān)測(cè) 對(duì)已建的大中商場(chǎng)要 求進(jìn)行改造 提出增設(shè)通風(fēng)設(shè)施或加建空氣調(diào)節(jié)裝置。經(jīng)營(yíng)商品也會(huì)有新的變換,這就要求空調(diào)系統(tǒng)和風(fēng)口布置要適應(yīng)這些變化等等。6)由于商業(yè)建筑人員頻繁進(jìn)出,而且易燃物品也較多,故必須遵守《建筑設(shè)計(jì)防火規(guī)范》和《高層民用建筑防火規(guī)范》等,對(duì)高層商業(yè)建筑和封閉性的地下商場(chǎng)等,應(yīng)配置排煙等防災(zāi)設(shè)備。因此這類建筑宜采用雙風(fēng)機(jī)系統(tǒng),或單風(fēng)機(jī)加排風(fēng)機(jī)系統(tǒng)。應(yīng)根據(jù)不同百貨商場(chǎng)的冷負(fù)荷大小和各地區(qū)能量的供給條件,允許接受電力的能力情況進(jìn)行選擇。 還有一種情況就是設(shè)計(jì)者有時(shí)會(huì)將高區(qū)低區(qū)的冷水機(jī)組截然分開,其實(shí)這是沒有必要的,因?yàn)楦邊^(qū)可采用通過換熱的辦法,使高低區(qū)的冷水機(jī)組合為一個(gè)系統(tǒng),這樣就可減少機(jī)組臺(tái)數(shù)。在公共和民用建筑中,中央空調(diào)系統(tǒng)的耗能約占建筑物耗能的 65 %以上。集中方式有可分為全空氣方式、與機(jī)組(指末端裝置)結(jié)合使用的方式(或空氣水方式)以及全水方式。百貨商店回風(fēng)口的允許風(fēng)速,位于人的活動(dòng)區(qū)域上面時(shí),允許面風(fēng)速4m/s,在人的活動(dòng)區(qū)域內(nèi)但原離人時(shí),允許面風(fēng)速34m/s ,在人的活動(dòng)區(qū)域內(nèi),但離人較近時(shí),允許面風(fēng)速23m/s。4) 風(fēng)口的數(shù)量選擇是根據(jù)實(shí)際需要,不宜過多設(shè)置;因風(fēng)口在商場(chǎng)內(nèi)外露,所以它的形狀和布置等的確定,應(yīng)征得建筑師的同意。 防火、防排煙1. 防火分區(qū)和防火分隔在高層建筑設(shè)計(jì)時(shí),防火和防煙分區(qū)的劃分是極其重要的。每個(gè)防煙分區(qū)的建筑面積不宜超過500m2,且防煙分區(qū)不應(yīng)跨越防火分區(qū)。根據(jù)建筑物的特點(diǎn)及分布,我們對(duì)該建筑進(jìn)行如下分區(qū):東區(qū)和西區(qū)。 圍護(hù)結(jié)構(gòu)冷負(fù)荷計(jì)算外墻:外墻瞬變溫差傳熱形成的冷負(fù)荷Q,可按下式計(jì)算: Q=KFΔtτζ (31)式中: K—外墻的傳熱系數(shù), W/㎡? F—外墻的面積, ㎡ τ—計(jì)算時(shí)刻; τζ—溫度波的作用時(shí)刻,即溫度波作用外墻外側(cè)的時(shí)刻; Δtτζ——作用時(shí)刻下,通過外墻的冷負(fù)荷計(jì)算溫差,簡(jiǎn)稱負(fù)荷溫差,℃,窗戶窗戶瞬變傳導(dǎo)得熱形成的冷負(fù)荷按下式進(jìn)行計(jì)算:Qτ=KF?tτ (32)式中: K—窗戶的傳熱系數(shù), W/㎡?℃F—窗口面積, ㎡?tτ—計(jì)算時(shí)刻的負(fù)荷溫差, ℃,見《空氣調(diào)節(jié)》課本附錄212. 因傳導(dǎo)負(fù)荷只與氣溫有關(guān),故按最熱月的日較差分區(qū),,傳熱系數(shù)較大,℃分檔。在工程上考慮到建筑物的用途和性質(zhì),熱濕負(fù)荷的特點(diǎn),溫濕度調(diào)節(jié)和控制的要求,空調(diào)機(jī)房的面積和位置,初投資和運(yùn)行維修費(fèi)用等諸多因素,應(yīng)選擇合理的空調(diào)系統(tǒng) 技術(shù)分析及空調(diào)方案的選擇 按空氣處理設(shè)備的設(shè)置情況分類1) 集中系統(tǒng):集中系統(tǒng)的所有空氣處理設(shè)備(風(fēng)機(jī)、冷卻器、加溫器、過濾器)都集中設(shè)在一個(gè)空調(diào)機(jī)房。所以此種系統(tǒng)只適用于小空間人