【正文】
的臺數(shù)和流量相對應(yīng), “一機一泵 ”的運行方式,并且設(shè)置一臺備用泵。 該設(shè)計中選用 了兩 管制 , 是因為 兩 管制系統(tǒng) 較為 簡單,初投資 較 少,實際 運行 中對室內(nèi)要求不高 。當 不平衡率大于 15%時,要重新調(diào)整 風管 尺寸;若仍不 能 滿足要求,則 可以采用 閥門 進行 調(diào)節(jié)。根據(jù)風管的水力計算,校核所選風機盤管及新風機組是否滿足余壓要求,能否保證送風口的風速,如能滿足,則選型符合條件,如不滿足,則應(yīng)該重新進行選型,選擇余壓較大 的型號,直到滿足為止。 散流器送風氣流組織設(shè)計計算 散流器平送方式,一般用于室溫允許 有一定 波動范圍,有技術(shù)夾層 、 層高較低的空調(diào)房間,送風射流沿著頂棚徑 向形 成貼附射流,保證 了 工作區(qū)穩(wěn)定均勻的溫度和風速。 風機盤管選型 表 61 風機盤管 選型 房間號 面積 ,2m 夏季室內(nèi)冷負荷 (全熱 ), W 室外焓值 ,kJ/kg 室內(nèi)焓值 ,kJ/kg 室內(nèi)外焓差 ,kJ/kg 風機盤管處理狀態(tài)點焓值 ,kJ/kg 風機盤管處理空氣焓差 , kJ/kg 風機盤管風量 , m3/h 風機盤管型號 臺數(shù) 1 層 1001 417 FP51 1 1002 248 2636 FP85 2 1003 420 4496 FP102 5 1004 463 FP51 1 1005 50 631 FP85 1 1007 63 703 FP85 1 1008 48 510 FP85 1 1009 385 FP51 1 1010 98 1138 FP68 2 1011 98 1457 FP85 2 1012 168 11697 FP102 3 1013 408 12072 FP136 6 2 層 2021 56 724 FP85 1 2021 352 50 11333 FP136 9 2021 220 49 7959 FP102 4 2021 50 13 365 FP51 1 2021 635 FP85 1 2021 624 FP85 1 標準層 4001 30 473 FP51 1 本科畢業(yè)設(shè)計(論文) 13 新風機組選型 空調(diào)系統(tǒng) 除了 滿足 對室內(nèi)環(huán)境的溫濕度控制外,還要給環(huán)境提供足夠的室外新鮮空氣。本次設(shè)計 中兩種都有涉及,一般的辦公室 采用風機盤管加新風系統(tǒng),新風 由 室外引入 , 經(jīng)過新風機組處理 , 再送到各房間風機盤管,與風機盤管處理過的室內(nèi)空氣混合后由風機盤管吹出, 且承擔房間內(nèi)的負荷, 各房間不單獨設(shè)置排風系統(tǒng),通過門窗縫隙滲透風量 。 ( 2) 與活塞式制冷機相比,螺桿式冷水機組沒有不平衡慣性力,也不存在液擊的問題,機組可平穩(wěn)的高速工作。特點是冬季鍋爐供暖,夏季鍋爐供蒸汽或熱水,作為溴化鋰吸收式冷水機組的動力,供冷時,安全性高、噪聲小 。 表 42 冷負荷匯總 表 房間號 夏季總冷負荷 (含新風 /全熱 ),W 夏季室內(nèi)負荷 (全熱 ),W 夏季總濕荷(含新風 ),kg/h 夏季室內(nèi)濕負荷 , kg/h 夏季新風負荷 , W 夏季新風濕負荷 , kg/h 建筑物 1 樓層 1001[消防控制室 ] 1002[資料室 ] 1003[辦公室 ] 1004[辦公室 ] 1005[辦公室 ,2] 1007[辦公室 ] 1008[辦公室 ] 1009[辦公室 ] 1010[工程師站 ] 1011[機柜間 ] 0 0 0 0 本科畢業(yè)設(shè)計(論文) 8 經(jīng)計算,得到整個辦公樓夏季的冷負荷為 ,采用 空調(diào) 采暖冬季的熱負荷為 。 ( 2)其他的房間如辦公室,休息室,會議室等 采用風機盤管 加新風 系統(tǒng),因為這部分房間負荷分布不均勻,使用功能和時間不統(tǒng)一,風機盤管系統(tǒng)具有較高的調(diào)節(jié)靈活性。全空氣空調(diào)系統(tǒng)通過輸送 熱濕處理過 的冷空氣向房間提供顯熱冷量和潛熱冷量,其空氣的冷卻、去濕 由 空調(diào)機房內(nèi)的空氣處理機組來完成,在房間內(nèi)不再進行補充冷量;而對輸送到房間內(nèi)的空氣的加熱可在空調(diào)機房內(nèi)完成,也可在各房間內(nèi)完成。 空氣水系統(tǒng):以空氣和水為介質(zhì),共同承擔室內(nèi)熱負荷、冷負荷。 ( 5) 本建筑為地上 十二 層、地下 一 層的高層建筑 ,每層高 米。 本科畢業(yè)設(shè)計(論文) 2 2 工程概述 工程概況 本次設(shè)計對象為北京某綜合辦公樓,其建筑面積約為 10700m2,該辦公樓共十二層,地下一層為車庫,一至三層為裙房,且有變形伸縮縫將每層分為兩部分,首層為接待大廳和一些辦公室,二層含有大餐廳、辦公室和 IT 中心,三層為辦公室,四層以上為標準層,以辦公室為主。而作為建筑業(yè)的重要組成 部分 的暖通空調(diào)業(yè),其新產(chǎn)品、新技術(shù) 、 新材料更是層出不窮。 System design。 畢 業(yè) 設(shè) 計 (論文 ) ` 題 目 北京某綜合辦公樓 暖通空調(diào)系統(tǒng)設(shè)計 二〇一六年六月 本科畢業(yè)設(shè)計(論文) I 北京某綜合辦公樓暖通 空調(diào)系統(tǒng)設(shè)計 摘要 本文 對 北京某綜合辦公樓暖通 空調(diào)系統(tǒng) 進行 設(shè)計, 對于每一環(huán)節(jié)的設(shè)計,都要提出幾種預選方案并比較各個方案的優(yōu)缺點及進行經(jīng)濟技術(shù)分析,最終得到最優(yōu)方案,來達到辦公樓暖通空調(diào)設(shè)計要求。 關(guān)鍵詞 :暖通空調(diào)系統(tǒng);系統(tǒng)設(shè)計;設(shè)計原理;節(jié)能設(shè)計;可持續(xù)發(fā)展 本科畢業(yè)設(shè)計(論文) II THE HVAC SYSTEM DESIGN OF A GENERAL OFFICE BUILDING IN BEIJING Abstract This paper on the design of the HVAC system of a general office building in Beijing, for every aspect of the design, I have proposed several preliminary scheme and pared the advantages and disadvantages of each scheme, made technical and economic analysis, finally get optimal solution to achieve the office building HVAC design requirements. In view of the problems in the design process, I also put forward some practical solutions to improve the program. Construction object for a prehensive office building in Beijing, one to three layers for the podium, room type has the atrium, restaurant, office, transformer room, IT center, four to ten in the office on the second floor is given priority to, considering the room type and use time, air conditioning system is fan coil plus fresh air in the form of, for the individual does not need to use only fresh air in the room fan coil units provide cold energy equipment room arrangement separately, using the two screw refrigeration unit, due to the cold and hot load were similar, traffic nearly two times, hot and cold water pump were set up respectively, equipme nt room inside the plate heat exchanger for municipal heat supply work and the secondary side heat transfer, used for water supply of heating in are some must pay attention to in the design of problems, such as duct pipe layout, selection of fan coil units, refrigeration room layout is reasonable, should be bined with the actual construction situation to determine the design scheme. The HVAC system design ply with the relevant national design specification, selection of equipment have access to a lot of design manual and sample, and through the parison of technology and economy, and ultimately determine the reasonable design, equipment selection, and the pletion of the construction plans of the rendering. this paper illustrates the design principle and method in detail, and the 本科畢業(yè)設(shè)計(論文) III related specific data are also reflected in this paper. Keywords: HVAC system。 暖通空調(diào)技術(shù)發(fā)展概況 隨著國民經(jīng)濟的快速持續(xù)發(fā)展,作為支柱產(chǎn)業(yè)之一的建筑業(yè)也得到迅猛發(fā)展。最后進行制冷機房相關(guān)設(shè)計,選擇合適的機房設(shè)備,繪制相關(guān)平面圖系統(tǒng)圖。 ( 3) 外窗:空氣層為 14mm 的熱防護玻璃窗,冬季 K= )( ℃mW/ 2 ? ,夏季 K= )( ℃mW/ 2 ? ( 4) 內(nèi)墻:輕集料混凝土框架填充墻,硬質(zhì)聚氨酯板, K= )( ℃mW/ 2 ? 。 全空氣系統(tǒng):全部用空氣承 擔室內(nèi)熱負荷、冷負荷。 全空氣系統(tǒng)方案 全空氣系統(tǒng)是完全由空氣來負擔房間的冷熱負荷的系統(tǒng)。 因為 空調(diào)房間面積大,使用時人員較集中,空調(diào)容量大,而且房間溫濕度參數(shù)、潔凈度要求 、使用時間等基本一致,易于統(tǒng)一控制管理 ,且利于節(jié)能。且有利于計算整棟樓的最大負荷。 ( 2) 溴化鋰吸收式冷水機組供冷,鍋爐供熱 : 制冷設(shè)備為熱水型吸收式冷水機組,制熱設(shè)備為燃氣鍋爐、電鍋爐或燃煤鍋爐。 選用螺桿式制冷機的優(yōu)點有: ( 1) 本螺桿壓縮機 運行零部件少,特別是沒有活塞式壓縮機的閥片組等易損件,因而運行可靠,壽命長。其形式主要有兩種:一 種 是新風不承擔房間 內(nèi) 的 冷 負荷, 另一種 是新風承擔房間 內(nèi) 的 冷 負荷。在選擇過程中,所選擇的風機盤管提供的冷量可能會比房間所需的冷量大很多,但在滿足衛(wèi)生要求的前提下,可用電動兩通閥門進行調(diào)節(jié)。 中庭部位 采用 的是 雙層百葉 風口 , 風機盤管系統(tǒng)送風口選 擇 的是 方形散流器 。 水力計算的目的是校核所選設(shè)備型號壓力能否滿足工作要求。 則沿程阻力根據(jù)公式 LRP ??? l 來計算 計算各管段的沿程阻力 和 局部阻力, 之和即為管路的總阻力, 并使各并聯(lián)管路之間的不平衡率不超過 15%。除了在全年中 多數(shù) 時間需要同時 進行供冷和供熱的建筑外, 其他 大部分空調(diào)建筑通常 是 冷凍水系統(tǒng)和熱水系統(tǒng)用同一個 管路系統(tǒng), 這樣 只需將冷水機組及其水泵或 者 熱源及其水泵并聯(lián)即可 ]14[ 。當流量較大時,也采用單級雙吸離心水泵;當高揚程小流量時,常采用 雙級 離心水泵。 ( 2) 補給水泵選取 用補給水泵定壓時,補給水泵的臺數(shù)應(yīng)選兩臺以上兼顧備用,可不考慮單獨設(shè)備