【正文】
K TS B 1K A 2K A 1K J 1S Q 3 K A K HH LH AS Q 4K M 1K J 2K TK M 2S Q 1Q F 1Q TA C 2 2 0 VA C 3 8 0 VQ KQ F 1K M 2K M 1K H主 電 路控 制 電 路 圖 5— 2 防火卷簾控制電路圖 河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 聯(lián)動(dòng)控制系統(tǒng) 27 噴淋泵聯(lián)動(dòng)控制 消防控制設(shè)備對(duì)自動(dòng)噴淋系統(tǒng)的控制,能控制噴淋泵的啟停。當(dāng)壓力升高后,壓力開關(guān)復(fù)位,KA1 觸點(diǎn)復(fù)位, KA失電、 KM1失電、 1號(hào)泵電機(jī)停止。排煙風(fēng)機(jī)的控制如圖55所示: 圖 5— 5 排煙風(fēng)機(jī)控制 排煙風(fēng)機(jī)的風(fēng)管上設(shè)排煙閥,這些排煙閥可以伸入幾個(gè)防火分區(qū)?;鹁蜂N時(shí),另送出 xK? 閉合指令停風(fēng)機(jī)。就地控制啟停與火警控制啟停合在一起,排煙閥直接由火警聯(lián)動(dòng)模塊控制,每個(gè) 火警聯(lián)動(dòng)模塊控制一個(gè)排煙閥?;鹁废?,則由火警聯(lián)動(dòng)模塊送出 K`停機(jī)信號(hào),使正壓風(fēng)機(jī)停。 圖 5— 3 全壓啟動(dòng)噴淋泵控制電路(壓力開關(guān)控制) 1)準(zhǔn)備工作狀態(tài):合上自動(dòng)開關(guān) QF1, QF2, QS,將 SA 至 “ 1 號(hào)泵自動(dòng), 2號(hào)泵備用”位置,電源指示燈 HL亮,噴淋泵處于準(zhǔn)備工作狀態(tài)。 當(dāng)來自火災(zāi)報(bào)警控制器的感溫聯(lián)動(dòng)觸 KJ2閉合時(shí),時(shí)間繼電器 KT 線圈通電延時(shí)動(dòng)作,卷簾門下降到位,完全閉合.其常開觸點(diǎn)閉合,接觸器 KM1 線圈斷電,其常開觸頭閉合,電動(dòng)機(jī)轉(zhuǎn)動(dòng),卷簾門繼續(xù)下降到達(dá)底部,碰觸微動(dòng)開關(guān) SQ4,其常駐閉觸點(diǎn)斷開,接觸器 KM1線圈通電,其常開觸頭打開,電機(jī)停轉(zhuǎn)。排煙口開啟的同時(shí),進(jìn)風(fēng)口也隨時(shí)開啟。火勢擴(kuò)大后,排煙風(fēng)道中的閥門在溫度達(dá)到 280℃時(shí)關(guān)閉,停止排煙(防止煙溫過高引起火災(zāi))。走道,樓梯間及電梯前室采用獨(dú)立的機(jī)械加壓送風(fēng)的防煙設(shè)施。當(dāng)采用常開的百葉風(fēng)口時(shí),應(yīng)在加壓送風(fēng)機(jī)出口處設(shè)置止回閥。因此,加壓部位在關(guān)閉門時(shí),必須與著火樓層保持一定的壓力差(該部位空氣壓力值為相對(duì)正壓) 。當(dāng)管道氣流溫度達(dá)到 280℃時(shí), 閥門靠裝有易熔金屬溫度熔斷器而自動(dòng)關(guān)閉,切斷氣流,防止火災(zāi)蔓延。 排煙口布置在防煙分區(qū)的中心,距最遠(yuǎn)點(diǎn)的水平距離為 30m。自然排煙不使用動(dòng)力,結(jié)構(gòu)簡單,運(yùn)行可靠,但當(dāng)火勢猛烈時(shí),火焰有可能從開口部噴出,從而使火勢蔓延;自然排煙還易受到室外風(fēng)力的影響,當(dāng)火災(zāi)房間處在迎風(fēng)側(cè)時(shí),由于受到風(fēng)壓的作用, 煙氣很難排出。 3)消防電梯的設(shè)置規(guī)定 ①消防電梯的載重量 不應(yīng)小于 800kg,廂內(nèi)裝修應(yīng)用不燃材料; ②消防電梯宜分別設(shè)在不同的防火分區(qū)內(nèi); ③消防電梯轎廂內(nèi)應(yīng)設(shè)專用電話,并應(yīng)在首層設(shè)置供消防隊(duì)員專用的操作按鈕; ④消防電梯間應(yīng)設(shè)前室,其面積:居住建筑不應(yīng)小于 ㎡ ,公共建筑不應(yīng)小于 ㎡ 。 應(yīng)急疏散照明設(shè)置 在本工程中,應(yīng)急照明和疏散標(biāo)志燈設(shè)在走道、樓梯轉(zhuǎn)彎處、 直通地下室樓梯的水平地面處, 并固定在距地面 1m的墻面上,且走道的指示標(biāo)志燈間距設(shè)置為20m。分為:自然排煙、機(jī)械加壓送風(fēng)排煙、機(jī)械排煙等。 ② 疏散出口:從房間連通疏散走道或門廳的門。煙霧的產(chǎn)生不僅會(huì)造成人員的中毒或窒息死亡,而且還導(dǎo)致火災(zāi)蔓延、引起人員恐慌,影響疏散與撲救。 3)設(shè)有手動(dòng)火災(zāi)報(bào)警按鈕、消火栓按鈕等處宜設(shè)置電話塞孔。 廣播功放的額定輸出功率應(yīng)是廣播揚(yáng)聲器總功率的 倍左右。系統(tǒng)的構(gòu)成如圖 3— 1 所示。 消防廣播系統(tǒng) 火災(zāi)應(yīng)急廣播揚(yáng)聲器的設(shè)計(jì)布置計(jì)算 根據(jù)海灣公司的產(chǎn)品: XDFT6404吸頂式音箱將定壓 120V音頻信號(hào)轉(zhuǎn)變?yōu)槁曇舨シ懦鋈?,具?3W 功率規(guī)格,主要性能指標(biāo)詳見產(chǎn)品選型。從一個(gè)防火分區(qū)內(nèi)的任何位置到最近的一個(gè)手報(bào)、消火栓的步行距離為 25m。 三到十五層: 房間 ①②③④ S1= ㎡,所以設(shè)置一只探測器。 房間③ S3= ㎡ , 由于 S3= ㎡﹤ A= 80 ㎡,所以設(shè)置一只探測器。 15176。 探測區(qū)域的劃分按獨(dú)立房間劃分,一個(gè)探測區(qū)域的面積不超過 500 ㎡ ,從主要入口能看清內(nèi)部,且面積不超過 1000 ㎡的房間,也 劃分為一個(gè)探測區(qū)域,另外樓梯間,電梯前室,走道,電梯井等都要作為獨(dú)立的探測區(qū)域。 本大樓 采用控制中心報(bào)警系統(tǒng),考慮到樓層較多,探測區(qū)域較多,故采用此河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 火災(zāi)自動(dòng)報(bào)警系統(tǒng) 5 系統(tǒng),用分散控制然后集中控制方式。 依據(jù)《高層民用建筑防火設(shè)計(jì)規(guī)范》故劃分為一類建筑,確定為一級(jí)保護(hù)對(duì)象。 3)安全疏散和防排煙系統(tǒng) 火災(zāi)發(fā)生時(shí)由煙感器感知,并在防災(zāi)中心顯示所在分區(qū)。 河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 緒論 2 內(nèi)容簡介 高層建筑的特點(diǎn)決定其火災(zāi)的危險(xiǎn)性和高層建筑的火災(zāi)自動(dòng)報(bào)警系統(tǒng)的重要性一套完整的火災(zāi)自動(dòng)報(bào)警系統(tǒng)是高層建筑發(fā)生火災(zāi)時(shí)人們生命財(cái)產(chǎn)的有利保障,是能否快速準(zhǔn)確地發(fā)現(xiàn)火情,把火災(zāi)撲滅在萌芽狀態(tài)的關(guān)鍵所在, 本設(shè)計(jì)主要由下面幾個(gè)部分組成: 1)火災(zāi)自動(dòng)報(bào)警系統(tǒng) 該大樓的自動(dòng)報(bào)警系統(tǒng)由火災(zāi)探測器、區(qū)域顯示器和集中報(bào)警器組成。第一代為全模擬量的火災(zāi)防控聯(lián)動(dòng)系統(tǒng),即工程上所指的( N+1)總線制系統(tǒng);第二代為地址編碼式的消防報(bào)警控制系統(tǒng);第三代為既有自動(dòng)巡檢功能的智能化火災(zāi)防控系統(tǒng)。智能建筑 是集現(xiàn)代科學(xué)技術(shù)之大成的產(chǎn)物。 關(guān)鍵詞 火災(zāi)自動(dòng)報(bào)警 聯(lián)動(dòng)控制 噴淋泵 河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 摘要 II Abstract Along with our country building (IB) of industry development, high building and construction group is more and more, thus appeared the intelligent building. Intelligent building to through the will of the building structure, equipment, services and management according to the needs of the users for optimum bination, thus to provide users with a high efficiency, fortable, convenient human architecture environment. Intelligent buildings with modern science and technology is a plete collection of the wellknown product. This paper designed a intelligent construction senior residential fire prevention and control system, fire control system is mainly induced institutions, namely detectors, alarm and alarm system, and its executive mechanism, and that is to be automatic water spray and indoor fire hydrant extinguishing system, fire extinguishing system and all kinds of doors and linkage control. This paper design content including automatic fire alarm system, firecontrol munication system, safe evacuation and smoke control system and linkage control system, etc. Key words autom atic fire alarm, linkage control, spray pump 河南城建學(xué)院本科畢業(yè)設(shè)計(jì)( 論文) 目錄 目 錄 摘 要 ..............................................................I Abstract ............................................................II 1 緒 論 ..............................................................1 選題的目的意義 ................................................1 國內(nèi)外研究綜述 ................................................1 內(nèi)容簡介 ......................................................2 所采用的研究方法和手段 ........................................2 2 火災(zāi)自動(dòng)報(bào)警系統(tǒng) ...................................................4 防火類別及等級(jí)的確定 ..........................................4 該大樓火災(zāi)自動(dòng)報(bào)警系統(tǒng)結(jié)構(gòu) 選型 ................................4 系統(tǒng)設(shè)計(jì) .................................................4 該大樓結(jié)構(gòu)選型 ..........................................4 報(bào)警區(qū)域及探測區(qū)域的劃分 ......................................5 探測區(qū)域劃分規(guī)定 ........................................5 該綜合大樓的探測區(qū)域的劃分 ..............................6 火災(zāi)探測器的選擇與設(shè)置 ........................................6 火災(zāi)探測器的設(shè)置要求 .....................................7 火災(zāi)探測器的布置 .........................................7 火災(zāi)探測器的數(shù)量計(jì)算 .....................................7 手動(dòng)火災(zāi)報(bào)警按鈕、消火栓按鈕的設(shè)置 ............................9 區(qū)域顯示器的布置 ..............................................9 水流指示器的布置 .............................................10 3 消防通訊系統(tǒng) ......................................................11 消防廣播系統(tǒng) .................................................11 火災(zāi)應(yīng)急廣播揚(yáng)聲器的設(shè)計(jì)布置計(jì)算 .......................11 火災(zāi)應(yīng)急廣播揚(yáng)聲器的設(shè)置 ...............................13 消防專用電話系統(tǒng) .............................................14 消防專用電話設(shè)計(jì)要求 ...................................14 消防專用電話的布置 .....................................15 4 安全疏散與防排煙系統(tǒng) ..............................................16 安全疏散誘導(dǎo)與防排煙系統(tǒng)的基本概念 ...........................16 河南城建學(xué)院本科畢業(yè)設(shè)計(jì)(論文) 目錄 應(yīng)急照明系統(tǒng)設(shè)計(jì) ......