【正文】
噴水強(qiáng)度/(L根據(jù)該建筑的結(jié)構(gòu)和使用性質(zhì),本系統(tǒng)選取動(dòng)作溫度為 68℃閉式吊頂型玻璃球噴頭。則 ..1??AL短邊為:28???LAB在最不利層劃分最不利作用面積,矩形的長(zhǎng)邊垂直于配水支管,短邊平行于配水支管。但是,相對(duì)而言,預(yù)作用系統(tǒng)造價(jià)要高一些。場(chǎng)所舉例如下表所示。V則, =15=9m3x (3hHb??16)式中 H——水箱與最不利點(diǎn)消火栓之間的幾何高差, mH2O; ——最不利消火栓栓口所需靜水壓,mH 2O;b h——水箱至最不利點(diǎn)消火栓之間管網(wǎng)的水頭損失,mH 2O。揚(yáng)程 63m,轉(zhuǎn)速 1450r/min,效率 73%,功率 30kw,汽蝕余量 。該工程室內(nèi)消火栓總用水量取 15L/s,帶入公式(39)得: <????所以可以確定,豎管管徑為 100mm,水平管為 125mm,進(jìn)水管為 150mm。根據(jù)公式(35)計(jì)算水槍噴口所需水壓。樓層 所在樓層高度 (m) 消火栓設(shè)置高度 (m) 充實(shí)水柱的長(zhǎng)度 (m) 規(guī)范要求的最小充實(shí)水柱(m)一層 10二層 3 10三層 3 10四層 3 10五層 3 10六層 3 10七層 3 10表 34 各樓層的充實(shí)水柱計(jì)算18根據(jù)規(guī)范要求,該工程充實(shí)水柱長(zhǎng)度取 12m,每個(gè)水槍流量按 5L/s 計(jì)算。一般情況下,當(dāng)水槍最小流量不大于 5L/s 時(shí),選用口徑 16mm 水槍(個(gè)別情況下,根據(jù)流量計(jì)算也可采用口徑 13mm 水槍) ;每支水槍最小流量大于 5L/s 時(shí),宜選用口徑 19mm 水槍(個(gè)別情況下, 根據(jù)流量計(jì)算,也可采用口徑 22mm 水槍) 。 5m,以防止建筑物上部物體墜落傷害操作人員;有困難時(shí),底層建筑物是外地上消火栓距建筑外墻距離可減少到 ?!督ㄒ?guī)》對(duì)建筑物的消防用水量做出以下規(guī)定:建筑物體積/m 3耐火等級(jí) 建筑物名稱及類別 ≤1 500 1 500~3 000 3 000~5000 5 000~20 000 20 000~50 000 >50 000甲、乙類 10 15 20 25 30 35丙類 10 15 20 25 30 40廠房丁、戊類 10 10 10 15 15 20甲、乙類 15 15 25 25 — —丙類 15 15 25 25 35 45倉(cāng)庫(kù)丁、戊類 10 10 10 15 15 20一、二級(jí)民用建筑 10 15 20 20 25 3015表 31 多層民用建筑物和工業(yè)建筑的室外消火栓用水量(L/s)建筑物名稱 體積 V消火栓用水量/(L適用場(chǎng)所:需防火隔離的開(kāi)口部位,如舞臺(tái)與觀眾之間的隔離水簾、消防防火卷簾的冷卻等。系統(tǒng)同時(shí)具備干式噴水滅火系統(tǒng)和濕式噴水滅火系統(tǒng)的特點(diǎn);克服了干式噴水滅火系統(tǒng)控火滅火率低,濕式系統(tǒng)產(chǎn)生水漬的缺陷,可以代替干式系統(tǒng)提高滅火速度。當(dāng)建筑物發(fā)生火災(zāi)火點(diǎn)溫度達(dá)到開(kāi)啟閉時(shí)噴頭時(shí),噴頭開(kāi)啟排氣、充水滅火。濕式自動(dòng)噴水滅火系統(tǒng)是世界上使用最早、應(yīng)用最廣泛、滅火速度快、控火率較高,系統(tǒng)比較簡(jiǎn)單的一種自動(dòng)噴水滅火系統(tǒng)。自動(dòng)噴水滅火系統(tǒng)是一種在發(fā)生火災(zāi)時(shí),能自動(dòng)打開(kāi)噴頭噴水滅火并同時(shí)發(fā)出火警信號(hào)的消防滅火設(shè)施,系統(tǒng)在火災(zāi)發(fā)生后能通過(guò)各種方式自動(dòng)啟動(dòng),并能同時(shí)通過(guò)加壓設(shè)備將水送入管網(wǎng)維持噴頭灑水滅火一定時(shí)間。注:耐火等級(jí)為一、二且可燃物較少的單層、多層丁、戊類廠房(倉(cāng)庫(kù)),耐火等級(jí)為三、四級(jí),且建筑體積不大于3 000m3的丁類廠房和建筑體積不大于5 000m3的戊類廠房(倉(cāng)庫(kù)),以及糧食倉(cāng)庫(kù)、金庫(kù),可不設(shè)置室內(nèi)消火栓。(9)高層廠房(倉(cāng)庫(kù))和高位消防水箱靜壓不能滿足最不利點(diǎn)消火栓水壓要求的其他建筑,應(yīng)在每個(gè)室內(nèi)消火栓處設(shè)置直接啟動(dòng)消防水泵的按鈕,并應(yīng)有保護(hù)設(shè)施。9(5)冷庫(kù)內(nèi)的消火栓應(yīng)設(shè)置在常溫穿堂或樓梯間內(nèi)。單元式、塔式住宅的消火栓宜設(shè)置在樓梯間的首層和各層消息平臺(tái)上。設(shè)置要求:室外地下或地面上、室內(nèi)地下室,或與室內(nèi)游泳池、水景水池兼用;應(yīng)設(shè)有水位控制閥的進(jìn)水管和溢水管、通氣管、泄水管、出水管及水位指示器等附屬裝置;根據(jù)各種用水系統(tǒng)的供水水質(zhì)要求是否一致,可將消防水池與生活或生產(chǎn)貯水池合用,也可單獨(dú)設(shè)置。單出口消火栓直徑有 50mm 和 65mm 兩種,雙出口消火栓直徑為 65mm。(1)消火栓設(shè)備:由消火栓、水帶、水槍和有玻璃門(mén)的消火栓箱組成。寒冷地區(qū)設(shè)置的室外消火栓應(yīng)有防凍措施。當(dāng)?shù)缆穼挾却笥?0m 時(shí),宜在道路兩邊設(shè)置消火栓,并宜靠近十字路口。目前地下消火栓有三種型號(hào),分別為SX6SX100 和 SX6510。在我國(guó)南方地區(qū)宜采用地上消火栓。 室外消火栓室外消火栓是設(shè)置在建筑物外面消防給水管網(wǎng)上的供水設(shè)施,主要供消防車從市政給水管網(wǎng)或室外消防給水管網(wǎng)取水實(shí)施滅火,也可以直接連接水帶、水槍出水滅火。、學(xué)校、電影院、劇院、禮堂、食堂、菜市場(chǎng)不應(yīng)超過(guò) 2 層或設(shè)置在三層及三層以上樓層。該酒店共七層,無(wú)地下層。它是世界上公認(rèn)的最為有效的自救滅火設(shè)施,應(yīng)用最廣泛,用量最大,且具有安全可靠,經(jīng)濟(jì)實(shí)用,滅火成功率高等優(yōu)點(diǎn)。消防用水可以取之于人工水源,如消火栓、人工消防水池;也可以取之于天然水源,如地表水或地下水。酒店業(yè)已成為現(xiàn)代經(jīng)濟(jì)的一項(xiàng)重要產(chǎn)業(yè)。一景城市花園酒店共有 58 間客房。本次設(shè)計(jì)主要是基于室內(nèi)消火栓系統(tǒng)和水噴淋系統(tǒng)的設(shè)計(jì),包括基本分類,組成部分,設(shè)計(jì)原則,然后詳細(xì)介紹主要設(shè)計(jì)流程和計(jì)算參數(shù),最后根據(jù)所設(shè)計(jì)的水系統(tǒng)進(jìn)行設(shè)計(jì)總結(jié)。 2022 屆畢業(yè)設(shè)計(jì)(論文)題 目:某酒店消防水系統(tǒng)設(shè)計(jì)專 業(yè): 消防工程班 級(jí): 消防 1101姓 名: 王 節(jié)指導(dǎo)老師: 周 平起訖日期: ~2022 年 6 月七層酒店酒店消防水系統(tǒng)設(shè)計(jì)摘要隨著現(xiàn)代經(jīng)濟(jì)發(fā)展,賓館酒店在生活中變得常見(jiàn)普遍。關(guān)鍵詞:酒店 消火栓系統(tǒng) 自動(dòng)噴水滅火系統(tǒng)Design of fire water system on sevenstory hotelABSTRACTHotels appear to be more and more mon in our lives with the increasing development of modern economy, acpanied by a high demand in fire extinguishing system due to the tremendous mobility of its faculty, large amount of inflammable materials in interior decoration, highly fire risks and so on.The project in this design is a sevenfloor mercial lowrise building, with the seven floors on the ground excluding those sub levels. The first floor is the lobby of the hotel, the second floor is the restaurant and entertainment places, and the other floors are guest rooms. It was required to be the Type Two building according to those devising rule, with slight level of dangers. There would be fire hydrant of 15L/s indoors. While the sprinkler system is in closed wet system, which is of 30L/s flow. And its sprayer is closed hung in 68℃, with its lift of 100mH2O. This design, based on fire extinguishing system and sprinkler system, includes its fundamental classifications, ponents, design principles, and then describes its main design procedures and calculating parameters, finally e to the overall fire extinguishing budgets of water supply system.Key words: hotel。登記簿顯示,前天晚上,這間酒店這間酒店一共開(kāi)出 54 間房,共有 67 人入住?,F(xiàn)代化星級(jí)酒店日益增多,功能和服務(wù)不斷翻新。因此建筑消防給水系統(tǒng)一直是國(guó)內(nèi)外建筑消防滅火的主要設(shè)施。據(jù)資料統(tǒng)計(jì):美國(guó)在發(fā)生的 81428 次火災(zāi)中,滅控率達(dá) %;澳大利亞和新西蘭,在發(fā)生的 5734 次火災(zāi)中。一層樓層高為 ,二至七層樓層高為 。四級(jí) 2 層 600 學(xué)校、食堂、菜市場(chǎng)、托兒所、幼兒園、老年人建筑、醫(yī)院等不應(yīng)設(shè)置在二層。是撲救火災(zāi)的重要消防設(shè)施之一。地上消火栓是由本體、進(jìn)水彎管、閥塞、出水口和排水口組成,本體應(yīng)有 1 個(gè)直徑為 100mm和 2 個(gè)直徑為 65mm 的栓口。(2)按壓力分,室外消火栓分為低壓消火栓和高壓消火栓。消火栓距離路邊不應(yīng)大于 2m,距離房屋外墻不宜小于 5m,高層建筑距離外墻不宜大于40m。(6)停車場(chǎng)的室外消火栓宜沿停車場(chǎng)周邊設(shè)置,且距離最近一排汽車不宜小于 7m,距離加油站或油庫(kù)不宜小于 15m。設(shè)置消防水泵的系統(tǒng),其消火栓箱應(yīng)設(shè)啟動(dòng)水泵的按鈕。每支水槍最小流量<,最小流量<5L/s 時(shí),宜選用65mm 消火栓。(7)消防水箱:消防水箱對(duì)撲救初期火災(zāi)起著重要作用。18 層及 18 層以下,單元式住宅和每層不超過(guò) 8 戶且建筑面積不超過(guò) 650m2的塔式住宅,當(dāng)設(shè)兩根消防豎管有困難時(shí),可設(shè)一根豎管,但必須采用雙閥雙出口型消火栓。(6)室內(nèi)消火栓的間距應(yīng)由計(jì)算確定。(10)設(shè)有室內(nèi)消火栓的建筑,應(yīng)在屋頂設(shè)一個(gè)裝有壓力顯示裝置的試驗(yàn)和檢查用消火栓,采暖地區(qū)可設(shè)在頂層出口處或水箱間內(nèi)。《高規(guī)》規(guī)定:(1)高層建筑必須設(shè)置室內(nèi)、室外消火栓給水系統(tǒng)。該系統(tǒng)是當(dāng)今世界是公認(rèn)的最為有效、應(yīng)用最廣泛的自救滅火設(shè)施,具有安全可靠、經(jīng)濟(jì)實(shí)用、滅火成功率高等優(yōu)點(diǎn)。系統(tǒng)組成:濕式噴水滅火系統(tǒng)是由閉式噴頭、管道系統(tǒng)、濕式報(bào)警閥、報(bào)警裝置和供水設(shè)施等組成。優(yōu)點(diǎn)是水漬損失小,對(duì)溫度無(wú)特殊要求。也可代替濕式系統(tǒng),用于管道和噴頭易于被損壞而產(chǎn)生噴水和漏水,造成嚴(yán)重水漬的場(chǎng)所;還可用于對(duì)自動(dòng)噴水滅火系統(tǒng)安全要求較高的建筑物中。滅火原理:該系統(tǒng)采用噴霧噴頭把水粉碎成細(xì)小的水霧滴之后噴射到正在燃燒的物質(zhì)表面,通過(guò)冷卻、窒息以及乳化、稀釋的同時(shí)作用實(shí)現(xiàn)滅火。s1)同時(shí)使用水槍數(shù)量/支每根豎管最小流量/(L 40m,以保證水帶科撲救的有效范圍。 根據(jù)本建筑的實(shí)際情況消火栓口徑選 65mm,水槍口徑為 19mm,麻質(zhì)水帶,長(zhǎng)度 25m,消火栓栓口離地高度為 。 消火栓間距及保護(hù)半徑計(jì)算間距,應(yīng)首先計(jì)算出消火栓的保護(hù)半徑 R 計(jì)算公式:(33)hcLRd??式中 c——水帶展開(kāi)時(shí)的彎曲折減系數(shù),一般取 ~; ——水帶長(zhǎng)度,m;dL h——水槍充實(shí)水柱長(zhǎng)度,m。f?????mfqH? (37)qxhB式中 ——水槍噴口的射流量,L/s;xhq ——水槍噴口造成某充實(shí)水柱所需的壓力,mH 2O;H ——水流特性系數(shù),與水槍噴口直徑有關(guān),見(jiàn)表 37。消火栓系統(tǒng)簡(jiǎn)圖如下圖所示 水 箱水 泵 123456圖 31 消火栓系統(tǒng)簡(jiǎn)圖則可以確定最不利消火栓為系統(tǒng)圖中的 3 號(hào)消火栓,最不利計(jì)算管路為系統(tǒng)圖中 2 至 5 管路。選用兩組該型號(hào)泵,一用一備。低層和多層建筑設(shè)置在建筑物的最高部位。火災(zāi)危險(xiǎn)等級(jí) 設(shè)置場(chǎng)所舉例輕危險(xiǎn)級(jí) 建筑高度為 24m 及以下的旅館、辦公樓;僅在走道設(shè)置閉式系統(tǒng)的建筑等26中危險(xiǎn)級(jí) Ⅰ級(jí)①高層民用建筑:旅館、辦公樓、綜合樓、郵政樓、金熔點(diǎn)新樓、指揮調(diào)度樓、廣播電視樓(塔)等②公共建筑:醫(yī)院、療養(yǎng)院;圖書(shū)館、檔案館、展覽館;影劇院、音樂(lè)廳和禮堂及其他娛樂(lè)場(chǎng)所;火車站和飛機(jī)場(chǎng)及碼頭的建筑;總建筑面積小于 5000m2 的商場(chǎng)、總建筑面積小于 1000m2 的地下商場(chǎng)等③文化遺產(chǎn)建筑:木結(jié)構(gòu)古建筑、國(guó)家文物保護(hù)單位等④工業(yè)建筑:食品、家用電器、玻璃制品等工廠的備料與生產(chǎn)車間等;冷藏庫(kù)、鋼屋架等建筑構(gòu)件Ⅱ級(jí)①民用建筑:書(shū)庫(kù)、舞臺(tái)、汽車汽車停車場(chǎng)、總建筑面積 5000m2 及以上的商場(chǎng)、總建筑面積 1000m2 及以上的地下商場(chǎng)、凈空高度不超過(guò) 8m、物品高度不超過(guò) 的自選商場(chǎng)等②工業(yè)建筑:棉毛麻絲及化纖的紡織、織物及制品、木材木器及膠合板、谷物加工、煙草及制品、飲用酒、皮革及制品、造紙及紙制品、制藥等工廠的備料與生產(chǎn)車間嚴(yán)重危險(xiǎn)級(jí)Ⅰ級(jí) 印刷廠