【正文】
地上部分比較復(fù)雜,防火分區(qū)比較多,且上、下層防火分區(qū)不對應(yīng),按豎井編號較好,如 AL—1—A AP 和 APE 等字母及數(shù)字含義: 1 代表一層; A1 代表 A 號豎井饋出的 1 號配電箱。 用戶配電箱設(shè)計(jì)圖 9 配電柜 /箱與配電回路的編號 大型項(xiàng)目往往低壓配電柜 /箱很多,低壓饋出回路就更多,往往會出現(xiàn)柜 /箱編號及線路編號重復(fù)的問題,造成在設(shè)計(jì)圖中查找及將來維護(hù)檢修的困難。 7 公共區(qū)域配電箱的設(shè)置 考慮到商業(yè)的公共區(qū)域?qū)硇枰窝b修,必須預(yù)留電源。 5 斷路器及導(dǎo)體的選擇 由于商業(yè)地產(chǎn)項(xiàng)目房間用途的不確定性,在選擇斷路器和導(dǎo)體時必須考慮一定的裕量以滿足調(diào)整造成的負(fù)荷變化。需要探討的是需要系數(shù)的選擇,這在現(xiàn)行規(guī)范、手冊及《統(tǒng)一技術(shù)措施》中也沒有明確的要求,根據(jù)多年的設(shè)計(jì)體會認(rèn)為,在配電最末端商鋪內(nèi)戶箱或?qū)优潆娤溆?jì)算時 Kx 一般取 1,在各回路干線計(jì)算時取 ~ ,在變電所各配電變壓器計(jì)算時取 ~ 。 關(guān)鍵詞:高層建筑;電氣設(shè)計(jì);配電;負(fù)荷計(jì)算 1 工程概況 本項(xiàng)目商業(yè)綜合大樓,總建筑面積為 405570m2,地上建筑面積 272330m2,地下建筑面積 133240m2,主體高度 99m。 current transformer for the 1000/50。 load calculation 1 Project Overview The mercial plex project, with a total construction area of 405570m2, on the ground floor area of 272330m2, underground construction area of 133240m2, the main height of 99m. Project ponents are: two office buildings, construction area is 70800m2, 28 layers, the standard story is . 2 Load Calculation 1) Load characteristics: electric load, much larger than the national civil engineering technical measures Large 120W/m2 indicators, especially in the electricity load more food, and different types of food and beverage catering different cultural backgrounds also high. 2) the uncertainty of a large load, because the mercial real estate rents are often based on market demand, and constantly adjust the nature of the shops, making the load in the dynamic changes. 3) There is no specification and technical measures in the different types of mercial projects refer to the detailed parameters of the shops, engineering design load calculation in the lack of data, in most cases to rely on staff with previous experience in engineering design calculations. Load the selection of parameters: for the above problems, the load calculation, the first developer of sales and good munication, to determine the form of layers of the forms and nature of floor area, which is calculated on the basis of electrical load basis。 followed to determine parameter index within the unit area of shops is also very important and plex because there is no clear indicator of the specification can refer to。 bus carrying capacity for the 1000A, this road can meet the maximum 1000A current load requirements, even if there is adjustment, power distribution switches and circuit can not make big changes. 6 layer distribution box set According to the division of layers of fire protection district, respectively numbered as A ~ K layers within the set level shaft for the retail lighting power distribution box, with one on one power supply shops in radial power. Should be noted that the forms of the plex layers of layers of fire partition, does not correspond to the lower, making some of shaft power in charge of the fire district at the same time, also responsible for the power supply adjacent to the fire district. At design time, using the principle of proximity, while also taking into account the burden of the whole trunk load conditions, so that each shaft as far as possible a more balanced load. 7 public area distribution box set Taking into account the future needs of the business redecoration of public areas must be reserved for power. Here the desi