【正文】
rge cities, which are supplied with directcurrent threewire systems. Such a supply is invariably obtained from synchronous converters. There are also certain types of motor loads in industrial plants, which require direct current.Because many cities have experience rapid growth, their substations have often reached the limits of their capacity. As a result, downtown distribution systems are often overworked and many need a major, overhaul, overhaul, or expansion. However, space is scarce. Downtown business owners do not want “ugly” new substation marring the area’s appearance, but nor do businesses and residents grid the prospect of grid disturbances.One example of a system capable of integrating equipment monitoring with substation automation is the GE Harris integrated Substation Control System (ISCS). The system can integrate data from both substation system and equipment online monitoring devices into a mon data base. The data can then be processed by an expert system into information on the status and health of monitored equipment using selfdiagnostic programs. This information is then sent to a CMMS for automatic generation and tracking of maintenance work orders leads directly to the significant efficiencies found with conditionbased maintenance programs.ABB Power and its industry partners have bined to develop the ABB Power System software. The system contains a diagnostic and maintenance system that reports necessary maintenance before failure. It allows utilities and industrial customers to easily expand from a single puter to a full system, without reengineering.the directional protection basisEarly attempts to improve powerservice reliability to loads remote from generation led to the dualline concept. Of course, it is possible to build two lines to a load, and switch the load to whichever line remains energized after a disturbance. But better service continuity will be available if both lines normally feed the load and only the faulted line is tripped when disturbances occur. shows a singlegenerator, twoline, singleload system with breakers properly arranged to supply the load when one line is faulted. For the arrangement to be effective it is necessary to have the proper relay application. Otherwise, the expensive power equipment will not be able to perform as planned. Consider the application of instantaneous and/or time delay relays on the four breakers. Obviously the type of the relay cannot coordinate for all line faults. For example, a fault on the line terminals of breaker D. D tripping should be faster than B, however, the condition reverses and B should be faster than D. It is evident that the relay protection engineer must find some characteristic other than time delay if relay coordination is to be achieved.The magnitude of the fault current through breakers B and D is the。[3] [S].北京:我在完成論文期間得到了景老師的精心指導和熱情幫助,為我們提供了良好的學習環(huán)境和不可多得的鍛煉機會。當然在保護配置方面,我自己認為還是存在許多的不足之處,如:在保護配置方面,為了保證基本要求,應該加裝自動裝置;對于線路方面的保護配置,我認為還應該進一步的細化;對于電纜的選擇,我認為還是有點模糊,有些東西還是理解不太深刻。 當然這次的設計還有一些上述不足之處,需要我不斷的去學習,去改進。當對繼電保護知識有了一定的了解后,指導老師景展及時給我們作了指導,使我們對畢業(yè)設計的任務及著手點有了明確的認識,自己的頭腦中也形成了此次畢業(yè)設計課題的一個大概框架。其中:;2) 保護的動作時限t2應與t1配合,即: (),故選用DS111型時間繼電器,~ s。3)由于其動作時間為0s,為防止其在線路上管型避雷器放電時誤動,~。繼電器的動作電流為: ()考慮到系統(tǒng)發(fā)展時仍能適應,選用DL11/50型電流繼電器,~50A,故動作電流整定值為30A。其中:1為靈敏度,5498為10kV側基準電流。其動作電流整定為: ≥ () () ()式中: ——配變低壓側母線故障時本線路最大三相短路電流;——10kV母線等值系統(tǒng)最大運行方式阻抗標么值;XL1——織布廠、膠木廠、印染廠線路正序阻抗標么值;其中:,5498為按100MVA為基準容量計算而得的10kV側基準電流;所有阻抗的標么值都100MVA為基準容量而獲得?!煽肯禂?shù), ——返回系數(shù), ——考慮電動機自起動使電流增大的自起動系數(shù),= () (線路負荷電流取電流互感器額定一次側電流) ()2) 繼電器的動作電流為: ()考慮到系統(tǒng)發(fā)展時仍能適應,選用DL11/20型電流繼電器,其動作電流的整定范圍為5~20A,故動作電流整定值為6A。4) 由于其動作時間為0s,為防止其在線路上管型避雷器放電時誤動,~。 35kV線路三段式電流保護整定計算 第一段 無時限電流速斷保護1) 應躲過d2點的最大短路電流整定。電流保護多采用三段式,即由電流速斷保護、限時電流速斷保護和過電流保護組成。3) 并列運行的平行線路,可裝設橫聯(lián)差動保護作主保護,并應以接于兩回線電流之和階段式保護或距離保護作為兩回線同時運行的后備保護及一回線斷開后的主保護及后備保護。2) 對雙側電源線路可裝設帶方向或不帶方向的電流電壓保護。對1~2km 雙側電源的短線路,當采用上述保護不能滿足選擇性、靈敏性或速動性的要求時,可采用帶輔 助導線的縱差保護作為主保護,并裝設帶方向或不帶方向的電流保護作后備保護??刹捎枚〞r限或反時限特性的繼電器。: () ()即:,冷卻風扇自起動。 過負荷保護:(后備保護)其動作電流按躲過變壓器額定電流來整定。本裝置靈敏度 () 滿足要求。即:實際整定匝數(shù)(匝) () = 4匝, . sυ= 1匝。f I —電流互感器的最大相對誤差。因此35kV為基本側。變壓器差動保護動作電流應滿足以下三個條件1) 應躲過變壓器差動保護區(qū)外出現(xiàn)的最大短路不平衡電流2) 應躲過變壓器的勵磁涌流3) 在電流互感器二次回路端線且變壓器處于最大負荷時,差動保護不應動作結合設計要求和實際條件只對其做縱差動保護的整定,所選繼電器型號為BCH—2型差動繼電器。輕瓦斯保護的動作值按氣體容積為250~300cm2整定,本設計采用280 cm2。 作用:用來反映變壓器內部故障和油面降低,它反應于油箱內部故障所產生的氣體或油箱漏油而動作,其中重瓦斯保護動作于跳開變壓器各電源側斷路器,輕瓦斯保護動作于信號。為了使快速動作的主保護實現(xiàn)選擇性,從而就造成了主保護不能保護線路的全長,而只能保護線路的一部分。即:為滿足系統(tǒng)穩(wěn)定和設備的要求,能以最快速度有選擇地切除被保護設備和線路故障的保護,就稱為主保護;當主保護或斷路器拒動時,用以切除故障的保護,就稱為后備保護。在本設計中,根據(jù)要求需裝設過電流保護、電流速斷保護、過負荷保護和瓦斯保護。對于高壓側為35kV及以上的總降壓變電所主變壓器來說,也應裝設過電流保護、電流速斷保護和瓦斯保護;在有可能過負荷時,也需裝設過負荷保護。④采用間歇角原理。4) 變壓器縱聯(lián)差動保護:是按照循環(huán)電流的原理構成。 1) 10kV線路電流速斷保護:是根據(jù)短路時通過保護裝置的電流來選擇動作電流的,以動作電流的大小來控制保護裝置的保護范圍;有無時限電流速斷和延時電流速斷,采用二相二電流繼電器的不完全星形接線方式,本設計選用無時限電流速斷保護。其中電流速斷保護為主保護,不帶時限,0s跳閘。3) 變壓器的不正常運行過負荷、由于外部短路引起的過電流、油溫上升及油位過低。就線路來講,其主要故障為單相接地、兩相接地和三相接地。最后計算短路電流和短路容量。短路計算點要選擇得使需要進行短路校驗的電氣元件有最大可能的短路電流通過。5)接地裝置的設計,也需用短路電流。2)在選擇電氣設備時,為了保證設備在正常運行和故障狀況下都能安全、可靠的工作。電容器具有投資省,有功功率損耗小,運行維護方便,故障范圍小等特點,因此采用并聯(lián)電容器進行無功補償。利用系數(shù)法以概率論為基礎,根據(jù)設備利用率并考慮設備臺數(shù)以及各臺間功率差異的影響確定計算負荷與平均負荷間的偏差量(這反映在最大系數(shù)中大于1的部分),從而求得最大負荷。但不適合用電設備臺數(shù)少,各臺間容量懸殊且工作制度不同時的電力負荷計算。常選用最大負荷班(即有代表性的一晝夜內電能消耗量最多的一個班)的平均負荷,有時也計算年平均負荷。2) 尖峰電流指單臺或多臺用電設備持續(xù)1秒左右的最大負荷電流。并且對于35kV的配電裝置,此接線方式的回路數(shù)多在8回以上或者連接電源較多,負荷較大時。,二次側采用單母線分段的總降壓變電所主電路圖這種主接線,其一次側的高壓斷路器跨接在兩路電源線之間,猶如一座橋梁,而處在線路斷路器的內側,靠近變壓器,因此稱為內橋式結線。這種主接線的運行靈活性也較好,供電可靠性同樣較高,適用于一、二級負荷的工廠。適用范圍 :①6~10kV配電裝置,出線回路數(shù)為6回及以上時;②35~63kV配電裝置,出線回路為4~8回時;③110220kV配電裝置,出線回路為3~4回時。主接線對變電所設備選擇和布置,運行的可靠性和經濟性,繼電保護和控制方式都有密切關系,是供電設計中的